Rockwell Automation 1771-VHSC , D17716.5.74 Very High S User Manual
Page 45

4–6
Configuring Your Module
Description
Bits
Word
Mode 4 (storeĆreset/start) used
1
0
0
bit 15
Invert signal bit for gate/reset terminal.
0 = Not inverted
1 = Inverted
Words 5
thru 12
Rollover value. When rollover value is reached, the counter value
becomes 000,000 and counting continues from that point. The range
for both MSD and LSD is 0 to 999.
Word 5
Rollover value. Most significant digit for counter 0.
Word 6
Rollover value. Least significant digit for counter 0.
Word 7
Rollover value. Most significant digit for counter 1.
Word 8
Rollover value. Least significant digit for counter 1.
Word 9
Rollover value. Most significant digit for counter 2.
Word 10
Rollover value. Least significant digit for counter 2.
Word 11
Rollover value. Most significant digit for counter 3.
Word 12
Rollover value. Least significant digit for counter 3.
Words 13
thru 20
Preset values. The preset value is loaded into the respective counter
when its preset bit is set. The preset count value overrides the current
count, and becomes the new count value in the counter. When a
preset value is loaded, the counter begins to count from that value.
Word 13
Preset value. Most significant digit for counter 0.
Word 14
Preset value. Least significant digit for counter 0.
Word 15
Preset value. Most significant digit for counter 1.
Word 16
Preset value. Least significant digit for counter 1.
Word 17
Preset value. Most significant digit for counter 2.
Word 18
Preset value. Least significant digit for counter 2.
Word 19
Preset value. Most significant digit for counter 3.
Word 20
Preset value. Least significant digit for counter 3.
Words 21
thru 24
The ranges of words 21 thru 24 depend on the mode selected in word
3, bits 00Ć02.
In encoder/counter mode or period/rate mode, these are scalar words,
and divide the incoming pulse train at the gate/reset terminal by a
predetermined integer (1, 2, 4, 8, 16, 32, 64 and 128). Default value
is 1.
In rate measurement mode, these are time base values. Range is in
milliseconds from 10ms to 2 seconds in 10ms intervals.
Word 25
bits 00Ć03
Allows you to tie the output to any of the 4 counters. Bits correspond
to the counters: bit 00 for counter 0, bit 01 for counter 1, bit 02 for
counter 2, and bit 03 for counter 3.
bits 04Ć15
Not used.
Word 26
Most significant digit of the ON value of output 0.
Word 27
Least significant digit of the ON value of output 0.
Word 28
Most significant digit of the OFF value of output 0.
Word 29
Least significant digit of the OFF value of output 0.
Words 30
thru 34
These words are a repeat of words 25 through 29 with the exception
of the output number. These words are for output 1.