Frequency set group (cont.) – Rockwell Automation 1305 AC Drive, Firmware 1.01-3.00 User Manual User Manual
Page 92
Chapter 5 – Programming
5-24
Frequency Set Group (cont.)
[Jog Frequency]
Parameter # 24
Factory Default 10.0 Hz
[Jog Frequency]
Parameter Type Read & Write
Minimum 0.0 Hz
This parameter sets the frequency the drive will output
when it receives a jog command.
Units 0.1 Hz
Maximum 400.0 Hz
[Prst/2nd Accel]
Parameter # 26
Factory Default “Preset”
[Prst/2nd Accel]
Parameter Type Read & Write
This parameter, along with the [Upper Presets] parameter,
determines which frequency source and Accel/Decel
parameters will be selected using the optional inputs SW1,
SW2 and SW3. Refer to charts on Pages 5-26 and 5-27.
Units None
Settings “Preset”
“2nd Accel”
[Upper Presets]
Parameter # 72
Factory Default “Disabled”
[Upper Presets]
Parameter Type Read & Write
This parameter along with the [Prst/2nd Accel] parameter
determines which frequency source and Accel/Decel
parameters will be selected using the optional inputs SW1,
SW2 and SW3. Refer to charts on Pages 5-26 and 5-27.
Units None
Settings “Enabled”
“Disabled”
[Accel Time 2]
Parameter # 30
Factory Default 10.0 Sec
[Accel Time 2]
Parameter Type Read & Write
Minimum 0.0 Sec
This value determines the time it will take the drive to ramp
from 0 Hz to [Maximum Frequency]. The rate is linear
unless [S Curve] is ‘‘Enabled.” It applies to any increase
in command frequency unless [Accel Time 1] is selected.
Refer to charts on Pages 5-26 and 5-27.
Units 0.1 Second
Maximum 3600.0 Sec