Chapter 6 – Troubleshooting and Fault Information
6-8
Table 6.B Bulletin 1305 Fault Descriptions (cont.)
Fault Name & Number
Fault Description
Action to Take
Serial Fault
An active local bus adapter is disconnected while it possesses
r
us u
Check for break in communications line.
Serial Fault
F10
An active local bus adapter is disconnected while it possesses
control of a local bus function.
Check for break in communications line.
Undervolt Fault
DC Bus voltage fell below the minimum value. [Line Loss
a l p r
e er s pr gr
ed
u
Monitor the incoming AC line for low voltage or line power
errup
Undervolt Fault
F4
DC Bus voltage fell below the minimum value. [Line Loss
Fault] parameter is programmed to “U Volt Run”.
Monitor the incoming AC line for low voltage or line power
interruption.
UV Short Fault
F41
Excessive current has been detected between these two drive
output terminals.
Check the motor and external wiring to the drive output terminals
for a shorted condition.
UW Short Fault
F42
Excessive current has been detected between these two drive
output terminals.
Check the motor and external wiring to the drive output terminals
for a shorted condition.
VW Short Fault
F43
Excessive current has been detected between these two drive
output terminals.
Check the motor and external wiring to the drive output terminals
for a shorted condition.
Note: HIM errors are located on page 6-11.