Advanced set up group (cont.) – Rockwell Automation 1305 AC Drive, Firmware 1.01-3.00 User Manual User Manual
Page 88

Chapter 5 – Programming
5-20
Advanced Set Up Group (cont.)
[Analog Invert]
Parameter # 84
Factory Default ‘‘Disabled”
[Analog Invert]
Parameter Type Read & Write
This parameter enables the inverting function for the 0-10
Volt and 4-20mA analog input signal at TB2.
Units None
Settings ‘‘Enabled”
Maximum Input Commands [Minimum Freq]
Minimum Input Commands [Maximum Freq]
Volt and 4-20mA analog input signal at TB2.
‘‘Disabled”
Maximum Input Commands [Maximum Freq]
Minimum Input Commands [Minimum Freq]
Figure 5.12 Analog Invert
[Maximum Frequency]
'
0 V
4 mA
Drive Output
y
10 V
20 mA
y
[Minimum Frequency]
'
Disabled
Enabled
[4-20mA Loss Sel]
Parameter # 81
Factory Default ‘‘Stop/Fault”
[4-20mA Loss Sel]
Parameter Type Read & Write
This parameter selects the drives reaction to a loss of a
2
s g
he he
ve [ re
en y So r e s
Units None
Settings ‘‘Stop/Fault”
Drive Stops and Issues ‘‘Hz Err Fault” (F29)
This parameter selects the drives reaction to a loss of a
4-20mA signal when the active [Frequency Source] is
2
IMPO TA T: The dr ve u pu
s
e
‘‘Hold/Alarm”
Drive Maintains Last Output Freq and sets an Alarm bit
2
s g
he he
ve [ re
en y So r e s
4-20mA. IMPORTANT: The drive output contacts can be
used
ssue
r s g
y se
g [O p
on
‘‘Max/Alarm”
Drive Outputs [Maximum Freq] and sets Alarm bit
used to issue an alarm signal by setting [Output 1 Config]
r [O p
2 on
r
‘‘Pre1/Alarm”
Drive Outputs [Preset Freq 1] and sets an Alarm bit
or [Output 2 Config] to “alarm”.
‘‘Min/Alarm”
Drive Outputs [Minimum Freq] and sets an Alarm bit