Masks group (cont.) – Rockwell Automation 1305 AC Drive, Firmware 1.01-3.00 User Manual User Manual
Page 111

Chapter 5 – Programming
5-43
Masks Group (cont.)
[Start Mask]
Parameter # 95
Factory Default 01111111
[Start Mask]
Parameter Type Read & Write
This parameter determines which adapters can issue start
commands.
Units Byte
Settings 1
0
Permit Control
Deny Control
[Jog Mask]
Parameter # 96
Factory Default 01111111
[Jog Mask]
Parameter Type Read & Write
This parameter determines which adapters can issue jog
commands.
Units Byte
Settings 1
0
Permit Control
Deny Control
[Reference Mask]
Parameter # 97
Factory Default 01111111
[Reference Mask]
Parameter Type Read & Write
This parameter determines which adapters can control the
switching between the available freq. reference sources.
IMPORTANT: Terminal Block (TB2) will have control unless
masked out.
Units Byte
Settings 1
0
Permit Control
Deny Control
[Accel Mask]
Parameter # 98
Factory Default 01111111
[Accel Mask]
Parameter Type Read & Write
This parameter determines which adapters can switch
between [Accel Time 1] and [Accel Time 2].
IMPORTANT: Terminal Block (TB2) will have control unless
masked out.
Units Byte
Settings 1
0
Permit Control
Deny Control
[Decel Mask]
Parameter # 99
Factory Default 01111111
[Decel Mask]
Parameter Type Read & Write
This parameter determines which adapters can switch
between [Decel Time 1] and [Decel Time 2].
IMPORTANT: Terminal Block (TB2) will have control unless
masked out.
Units Byte
Settings 1
0
Permit Control
Deny Control