Rockwell Automation 1305 AC Drive, Firmware 1.01-3.00 User Manual User Manual
Page 103
Chapter 5 – Programming
5-35
Faults
This group of parameters provides information and programmed settings on commonly viewed drive faults.
[Fault Buffer 0-3]
Parameter # 86-89
Factory Default None
[Fault Buffer 0-3]
Parameter Type Read Only
These parameters store the last (4) faults that occur. If the
same fault occurs multiple times in a row, it will only be
stored once. [Fault Buffer 0] through [Fault Buffer 3] can
only be cleared by ‘‘Reset Defaults” from EEPROM mode
or [Set Defaults] parameter. This will leave a ‘‘F48” in
[Fault Buffer 0].
Units None
Buffer
0
1
2
3
Last Fault, stored in EEPROM
Fault from Buffer 0, Stored in EEPROM
Fault from Buffer 1, Stored in EEPROM
Fault from Buffer 2, Stored in EEPROM
[Clear Fault]
Parameter # 51
Factory Default ‘‘Ready”
[Clear Fault]
Parameter Type Read & Write
This parameter is used to clear a fault and return the drive
to ready status if the fault condition no longer exists.
IMPO TA T: C e r
u ]
s p ru
g dr ve
s
Units None
Displays ‘‘Ready”
Display after function complete
IMPORTANT: [Clear Fault] will stop a running drive. Also
[Clear Fault] does not clear [Fault Buffer 0] through
[Fault Buffer 3].
‘‘Clear Fault”
Attempts to clear fault
[Cur Lim Trip En]
Parameter # 82
Factory Default ‘‘Default Run”
[Cur Lim Trip En]
Parameter Type Read & Write
This setting determines whether or not exceeding the
se
g
[
rren L
use D g s
Curre
Units None
Setting ‘‘Trip @ I Lim”
A Diagnostic Current Limit Fault is generated
setting in [Current Limit] will cause a Diagnostic Current
Limit Fault (Fault F36).
‘‘Default Run”
No fault generated
[Line Loss Fault]
Parameter # 40
Factory Default ‘‘F03 Enable”
[Line Loss Fault]
Parameter Type Read & Write
This setting determines whether a 15% drop in DC Bus
v
ge
h ve
e e
per
r
use ‘‘
er
Units None
Setting ‘‘UVolt Run”
‘‘Power Loss Fault” Disabled
voltage will have no effect on operation or cause a ‘‘Power
Loss Fault” (fault F03).
‘‘FO3 Enable”
Drive Trips at 85% of nominal bus voltage.