Output configuration group (cont.) – Rockwell Automation 1305 AC Drive, Firmware 1.01-3.00 User Manual User Manual
Page 102
Chapter 5 – Programming
5-34
Output Configuration Group (cont.)
[Analog Out Sel]
Parameter # 25
Factory Default “Frequency”
[Analog Out Sel]
Parameter Type Read & Write
This parameter selects the value to which the 0-10V DC
g u pu
T 2
er
s pr p r
Units None
Setting ‘‘Frequency”
0 to [Maximum Freq]
This parameter selects the value to which the 0-10V DC
analog output at TB2-5 terminal is proportional.
‘‘Current”
0 to 200% of Rated Drive Output Current)
g u pu
T 2
er
s pr p r
‘‘Bus Volts”
0 to Maximum Bus Voltage– 410V/230V Drives
815V/460V Drives
‘‘Power”
0 to 200% of Drive Rated OutputPower
[Above Freq Val]
Parameter # 77
Factory Default 0 Hz
[Above Freq Val]
Parameter Type Read & Write
Minimum 0 Hz
This parameter is used when [Output 1 Config] or
[Output 2 Config] is set to ‘‘Above Freq” to indicate when
the drive is operating above the specified frequency
setting.
Units Hertz
Maximum 400 Hz
IMPORTANT: This parameter can not be pro-
grammed while the drive is running.
[Above Curr Val]
Parameter # 142
Factory Default 0 % of Drive Rated Current ➀
[Above Curr Val]
Parameter Type Read & Write
Minimum 0 % of Drive Rated Current ➀
This parameter is used when [Output 1 Config] or
[Output 2 Config] is set to ‘‘Above Curr” to indicate when
the drive output current exceeds this value.
Units 1%
Maximum 150% of Drive Rated Current ➀
➀
The drive rated output current is based on three phase input ratings. See page 5-13
for Single Phase Input Rating instructions.