Rockwell Automation 1305 AC Drive, Firmware 1.01-3.00 User Manual User Manual
Page 16

Chapter 1 – Information and Precautions
1-6
Table 1.A Drive Rating and Derating Guidelines
a alo
Motor Rating
Voltage
a n
Catalog
er
3
O Input
1
O Input
ol a e
Rating
Number
IP30
HP
kW
Output ➀➁
Current (A)
HP
kW
Output ➀➁
Current (A)
1305-AA02A
1/2
0.37
2.3
–
–
–
200-230V
/6
1305-AA03A
3/4
0.55
3
1/2
0.37
2.3
2
2
50/60 Hz
1305-AA04A
1
0.75
4.5
3/4
0.55
3
1305-AA08A
2
1.5
8
1
0.75
4.5
1305-AA12A
3
2.2
12 ➂
2
1.5
8 ➂
1305-BA01A
1/2
0.37
1.3
380-460V
/6
1305-BA02A
3/4
0.55
1.6
8
6
50/60 Hz
1305-BA03A
1
0.75
2.3
N
v
e
1305-BA04A
2
1.5
4
Not Available
1305-BA06A
3
2.2
6 ➃
1305-BA09A
5
4.0
9 ➄
In general:
When operating the drive in an ambient temperature at or near
the maximum operating temperature (50
°
C), the following
derating guidelines are recommended to guard against
overheating depending on application and operating conditions.
➀
Motor Full Load Amps (FLA) should not exceed the drive output current rating.
➁
If the [PWM Frequency] is set above 4kHz, the output current must be derated per the
chart on page 5-20.
➂
Output current value listed for 200V input voltage. At 230V input voltage, output
current is 9.6A for 3 phase and 6.8A for single phase.
➃
Output current value listed for 380V input voltage. At 415V input voltage, output
current is 5.3A. At 460V input voltage, output current is 4.8A.
➄
Output current value listed for 380V input voltage. At 415V input voltage, output
current is 8.4A. At 460V input voltage, output current is 7.6A.