beautypg.com

Advanced set up group (cont.) – Rockwell Automation 1305 AC Drive, Firmware 1.01-3.00 User Manual User Manual

Page 84

background image

Chapter 5 – Programming

5-16

Advanced Set Up Group (cont.)

[Break Voltage]

Parameter # 50

Factory Default 0 Volts

[Break Voltage]

Parameter Type Read & Write

Minimum 0 Volts

This parameter sets the voltage the drive will output at
[Break Frequency]. Combined with [Break Frequency],
this value determines the Volts-per-Hz ratio between 0 and
[Break Frequency]. IMPORTANT: [DC Boost Select]
must be set to ‘‘Break Point” for this parameter to be
active.

Units 1 Volt

Maximum 50% of Max. Drive Rated Volts

[Maximum Voltage]

Parameter # 20

Factory Default Max. Drive Rated Volts

[Maximum Voltage]

Parameter Type Read & Write

Minimum 25% of Max. Drive Rated Volts

This parameter sets the highest voltage the drive will
output.

Units 1 Volt

Maximum 100% of Max. Drive Rated Volts

[Base Voltage]
[Base Frequency]

Maximum

'

a [Maximum Voltage]
[Maximum Frequency]

b

y

Motor Rated

Maximum

0 –

0

Voltage

Frequency

b

[Break Voltage]
[Break Frequency]

Start Boost

'

y

Motor Rated

'

Figure 5.7 Custom Volts-per-Hz Pattern

This pattern is active only when
[DC Boost Select] is set to
‘‘Break Point.”

The following guidelines should be followed when setting up
a custom Volts-per-Hz curve:

1.

[Maximum Voltage] must be greater than [Base Voltage].

2.

[Base Voltage] must be greater than [Start Boost].

3.

If [DC Boost Select] is set to “Break Point” then:

[Base Voltage] must be greater than [Break Voltage] and
[Break Voltage] must be greater than [Start Boost].