B–20, Read product text, Figure b.14 shows a read product text request – Rockwell Automation 1203-SM1 SLC to SCANport Communication Module User Manual
Page 86
![background image](/manuals/578915/86/background.png)
SCANport Messaging
B–20
Publication 1203–5.9 –– October 1996
Read Product Text
The Read Product Text message lets you request the product text
from the SCANport device. The following is an example of this
request:
Service=Get Attribute Single
Internal A–B Vendor Specific Class
Instance
Attribute
Data Length=0 Bytes
M0:e.000
M0:e.001
M0:e.002
M0:e.003
M0:e.004
000e
0092
0000
0001
0000
Value
Read Product Text
Service=Get Attribute Single
Internal A–B Vendor Specific Class
Instance
Attribute
Data Length=18 Bytes
M1:e.100
M1:e.101
M1:e.102
M1:e.103
M1:e.104
000e
0092
0000
0001
0012
Value
Response
Product Name String (Chars Lo=1st, Hi=2nd)
Product Name String (Chars Lo=3rd, Hi=4th)
Product Name String (Chars Lo=5th, Hi=6th)
Product Name String (Chars Lo=7th, Hi=8th)
Product Name String (Chars Lo=9th, Hi=10th)
M1:e.105
M1:e.106
M1:e.107
M1:e.108
M1:e.109
7542
206C
3331
3633
5020
Product Name String (Chars Lo=11th, Hi=12th)
M1:e.110
554c
Product Name String (Chars Lo=13th, Hi=14th)
Product Name String (Chars Lo=9th, Hi=10th)
M1:e.111
M1:e.112
2053
2020
Discard
M1:e.113
0000
Figure B.14 shows a Read Product Text request.
Figure B.14
Example of Read Product Text
address 0 1 2 3 4 5 6 7 8 9
N10:0 000e 0092 0000 0001 0000
address 0 1 2 3 4 5 6 7 8 9
N11:0 000e 0092 0000 0001 0012 7542 206c 3331 3633 5020
N11:10 554c 2053 2020 0000