Rockwell Automation 1203-SM1 SLC to SCANport Communication Module User Manual
Page 45
4–17
Using Enhanced Mode
Publication 1203–5.9 –– October 1996
Figure 4.13
Example G File Configuration
address 15 data 0
G1:0 0000 0000 0000 0000 Reserved (Used by SLC)
G1:1 0000 0000 0000 0000 Datalink Enables
|||| |||| |||| ||||
++++ |||| |||| |||+––– Channel 1 Datalink A Enable
| |||| |||| ||+–––– Channel 1 Datalink B Enable
| |||| |||| |+––––– Channel 1 Datalink C Enable
| |||| |||| +–––––– Channel 1 Datalink D Enable
| |||| ||||
| |||| |||+–––––––– Channel 2 Datalink A Enable
| |||| ||+––––––––– Channel 2 Datalink B Enable
| |||| |+–––––––––– Channel 2 Datalink C Enable
| |||| +––––––––––– Channel 2 Datalink D Enable
| ||||
| |||+––––––––––––– Channel 3 Datalink A Enable
| ||+–––––––––––––– Channel 3 Datalink B Enable
| |+––––––––––––––– Channel 3 Datalink C Enable
| +–––––––––––––––– Channel 3 Datalink D Enable
|
+––––––––––––––––––– Not Used
G1:2 0000 0000 0000 0000 Safe State Data – Channel 1 Logic Command
G1:3 0000 0000 0000 0000 Safe State Data – Channel 1 Reference
G1:4 0000 0000 0000 0000 Safe State Data – Channel 2 Logic Command
G1:5 0000 0000 0000 0000 Safe State Data – Channel 2 Reference
G1:6 0000 0000 0000 0000 Safe State Data – Channel 3 Logic Command
G1:7 0000 0000 0000 0000 Safe State Data – Channel 3 Reference
G1:8 0000 0000 0000 0000 Safe State Data – Channel 1 Datalink A1
G1:9 0000 0000 0000 0000 Safe State Data – Channel 1 Datalink A2
G1:10 0000 0000 0000 0000 Safe State Data – Channel 1 Datalink B1
G1:11 0000 0000 0000 0000 Safe State Data – Channel 1 Datalink B2
G1:12 0000 0000 0000 0000 Safe State Data – Channel 1 Datalink C1
G1:13 0000 0000 0000 0000 Safe State Data – Channel 1 Datalink C2
G1:14 0000 0000 0000 0000 Safe State Data – Channel 1 Datalink D1
G1:15 0000 0000 0000 0000 Safe State Data – Channel 1 Datalink D2
G1:16 0000 0000 0000 0000 Safe State Data – Channel 2 Datalink A1
G1:17 0000 0000 0000 0000 Safe State Data – Channel 2 Datalink A2
G1:18 0000 0000 0000 0000 Safe State Data – Channel 2 Datalink B1
G1:19 0000 0000 0000 0000 Safe State Data – Channel 2 Datalink B2
G1:20 0000 0000 0000 0000 Safe State Data – Channel 2 Datalink C1
G1:21 0000 0000 0000 0000 Safe State Data – Channel 2 Datalink C2
G1:22 0000 0000 0000 0000 Safe State Data – Channel 2 Datalink D1
G1:23 0000 0000 0000 0000 Safe State Data – Channel 2 Datalink D2
G1:24 0000 0000 0000 0000 Safe State Data – Channel 3 Datalink A1
G1:25 0000 0000 0000 0000 Safe State Data – Channel 3 Datalink A2
G1:26 0000 0000 0000 0000 Safe State Data – Channel 3 Datalink B1
G1:27 0000 0000 0000 0000 Safe State Data – Channel 3 Datalink B2
G1:28 0000 0000 0000 0000 Safe State Data – Channel 3 Datalink C1
G1:29 0000 0000 0000 0000 Safe State Data – Channel 3 Datalink C2
G1:30 0000 0000 0000 0000 Safe State Data – Channel 3 Datalink D1
G1:31 0000 0000 0000 0000 Safe State Data – Channel 3 Datalink D2