Bulletin 1402 Technical Specifications
INPUTS:
Current
0 to 5A RMS Cont., 200A RMS 1 Second
Frequency
40 to 100 Hz (steady-state)
Dielectric Withstand Voltage
2500V RMS
Current Input Burden
0.05 VA
Voltage
120V RMS (339 Vpk-pk) Maximum Peak
Voltage Input Impedance/Burden
728K
W/0.02 VA
SYNCHRONIZATION WINDOW:
Independent Upper & Lower Thresholds
Voltage
0.05% steps
Frequency
0.01 Hz steps
Phase
1 degree steps
ISOLATED LOAD SHARING INPUT/OUTPUT:
Max. Common Mode Voltage
240V AC
Continuous Voltage
2 to 4V DC
Input Impedance
45K
W
BACK PLANE POWER REQUIREMENTS:
1.1A at 5V DC (2.2A, 5 ms Inrush)
ENVIRONMENTAL:
Operating Temperature
0
°
to +60
°
C
Storage Temperature
–40
°
to +100
°
C
Humidity
5% to 95%, non-condensing
UPDATE RATE:
Synchronizing Bus Error Parameters — 100 milli-seconds
Load Share and Monitor Parameters —
200 milliseconds (Synchronization Inactive)
1 second (Synchronization Active)
ACCURACY:
@ 25
_ C
Current Measurement= +/–0.2% of Full Scale (Full Scale=1.4 x CT Primary)
Voltage Measurement= +/–0.2% of Full Scale (Full Scale=1.25 x PT Primary)
Frequency Measurement= +/–0.05 Hz (Within the 47 to 63 Range)
Slip Frequency= +/–0.05 Hz (Within the 47 to 63 Range)
Power, Power Factor, VA= +/–0.4% of Full Scale Power Consumption
(Full Scale=1.75 x CT Primary x PT Primary)
CERTIFICATION
Agency Certification
(when product or packaging is marked)
•
CSA certified
•
CSA Class I, Division 2
Groups A, B, C, D certified
•
UL listed
•
CE marked for all applicable directives