Rockwell Automation 1402-LSM Line Synchronization Module Installation Instructions User Manual
Page 32
Chapter 3
General Operation
3–10
Discrete Outputs (From the PLC Processor)
The following discrete output control signals will be provided from the
PLC–5 processor via the back plane:
•
Initiate Synchronization
•
Auto–Synchronization Mode
•
Check Synchronization Mode
•
Permissive Synchronization Mode
•
Load Share Disable
•
Isochronous/Droop Mode
•
Enable Single Phase Synchronization
Discrete Inputs (To the PLC Processor)
The following discrete input control signals will be provided to the PLC–5
processor via the back plane:
•
Module Status
•
Raise Voltage
•
Lower Voltage
•
Raise Speed –– frequency adjust
•
Lower Speed –– frequency adjust
•
Raise Speed –– phase adjust
•
Lower Speed –– phase adjust
•
Raise Power –– load share adjust
•
Reduce Power –– load share adjust
•
Close Breaker
•
Synchronization Failure
•
Power–up Bit
Block Transfer Data Interface
The LSM is capable of exchanging large amounts of data with the PLC
processor via the Block Transfer mechanism. The amount of data greatly
exceeds that which could be accommodated by a single block transfer. As a
result, the data is divided into several different “files” and can be obtained
through the use of multiple Block Transfers. The sizes, structure, and
contents of the block transfer reads and writes supported by the LSM are
provided in Appendix B. See “Block Transfer Communications”, listed on
Page 4–2 in the Application Information chapter of this manual for further
details on using Block Transfers.
PLC Interface Continued