Rockwell Automation 1402-LSM Line Synchronization Module Installation Instructions User Manual
Page 50

Appendix B
Block Transfer and Discrete
I/O Definition
B–2
Table B.2
Factory Configuration Parameters
Parameter
Number
Word
Num-
ber
Description
Range
Modulus
1 – Wye
1
1
Voltage Mode
2 – Delta
10
0
1
1
V
4 – Open Delta
1
2
2
PT Primary Rating – Volts
0 – 999
10
0
2
3
V
[Limits 120 – 115,000]
0 – 115
10
3
3
4
Line CT Primary Rating – Amps
0 – 999
10
0
3
5
[Limits 5 – 10,000]
0 – 10
10
3
4
6
Neutral CT Primary Rating – Amps
0 – 999
10
0
4
7
[Limits 5 – 10,000]
0 – 10
10
3
5
8
Synchronization Method
0=Delayed Accep-
1
5
8
Synchronization Method
tance Window
10
0
9
Voltage Match Error Upper Acceptance
±
999
1
–3
9
Voltage Match Error Upper Acceptance
Limit in Percent (Step size is 0.05 %)
±
0 – 999
10
–3
6
10
Limit in Percent (Step size is 0.05 %)
[Limits 0 – 25 %]
±
0 – 25
10
0
11
Voltage Match Error Lower Acceptance
±
999
1
–3
7
11
Voltage Match Error Lower Acceptance
Limit in Percent (Step size is 0.05 %)
±
0 – 999
10
–3
7
12
Limit in Percent (Step size is 0.05 %)
[Limits 0 – 25 %]
±
0 – 25
10
0
13
Frequency Match Error Upper Acceptance
±
999
1
–3
13
Frequency Match Error Upper Acceptance
Limit in Hz (Step size is 0.01 Hz)
±
0 – 999
10
–3
8
14
Limit in Hz (Step size is 0.01 Hz)
[Limits 0 – 1]
±
0 – 1
10
0
1
Frequency Match Error Lower Acceptance
±
999
1
–3
9
15
Frequency Match Error Lower Acceptance
Limit in Hz (Step size is 0.01 Hz)
±
0 – 999
10
–3
9
16
Limit in Hz (Step size is 0.01 Hz)
[Limits 0 – 1]
±
0 – 1
10
0
10
17
Phase Match Error Upper Acceptance
Limit in Degrees
±
0 – 20
10
0
11
18
Phase Match Error Lower Acceptance
Limit in Degrees
±
0 – 20
10
0
12
19
Acceptance Window Delay in Seconds
0 – 999
10
–3
12
20
(Step size 0.05 sec.)
[Limits 0 – 10]
0 – 10
10
0
13
21
–––
–––
13
22
Reserved for Product Expansion
–––
–––