beautypg.com

Rockwell Automation 1395 Digital Reference Adapter Board User Manual

Page 46

background image

Chapter 5

Programming Parameters

5-21

Parameter 591 – [A > Digital In 9]
Parameter 541 – [B > Digital In 9]

Use : Maps Digital Input 9
Programming Terminal units: None
Minimum Value: 0 (#1), 16 (#2)
Maximum Value: 15 (#1), 31 (#2)
Default Value: 1
Description: This parameter performs two functions. It determines
which bit of the two Digital Input Fast parameters will be controlled by
Digital In 9 (Terminal TB3-51). Entering a value of 0 – 15 will control
bits 0 – 15 of the Digital Input 1 Fast ( param 400), while entering a
value of 16 – 31 will control bits 0 – 15 of the Digital Input 2 Fast
(param 405). Refer to the description of Digital In 1 for more
information on programming. Connecting Digital In 9 to a positive
control voltage will cause the bit specified by this parameter to be set
to 1.

Parameter 592 – [A > Digital In 10]
Parameter 542 – [B > Digital In 10]

Use : Maps Digital Input 10
Programming Terminal units: None
Minimum Value: 0 (#1), 16 (#2)
Maximum Value: 15 (#1), 31 (#2)
Default Value: 1
Description: This parameter performs two functions. It determines
which bit of the two Digital Input Fast parameters will be controlled by
Digital In 10 (Terminal TB3-52). Entering a value of 0 – 15 will control
bits 0 – 15 of the Digital Input 1 Fast (param 400), while entering a
value of 16 – 31 will control bits 0 – 15 of the Digital Input 2 Fast
(param 405). Refer to the description of Digital In 1 for more
information on programming. Connecting Digital In 10 to a positive
control voltage will cause the bit specified by this parameter to be set
to 1.

Parameter 599 – [A > GA: Version]
Parameter 549 – [B > GA: Version]

Use : Maps Software Version #
Programming Terminal units: None
Description: This non changeable parameter is used to display the
version of the Digital Reference Adapter Board firmware.