Chapter 5
Programming Parameters
5-20
Parameter 588 – [A > Digital In 6]
Parameter 538 – [B > Digital In 6]
Use : Maps Digital Input 6
Programming Terminal units: None
Minimum Value: 0 (#1), 16 (#2)
Maximum Value: 15 (#1), 31 (#2)
Default Value: 8
Description: This parameter performs two functions. It determines
which bit of the two Digital Input Fast parameters will be controlled by
Digital In 6 (Terminal TB3-48). Entering a value of 0 – 15 will control
bits 0 – 15 of the Digital Input 1 Fast (param 400), while entering a
value of 16 – 31 will control bits 0 – 15 of the Digital Input 2 Fast
(param 405). Refer to the description of Digital In 1 for more
information on programming. Connecting Digital In 6 to a positive
control voltage will cause the bit specified by this parameter to be set
to 1.
Parameter 589 – [A > Digital In 7]
Parameter 539 – [B > Digital In 7]
Use : Maps Digital Input 7
Programming Terminal units: None
Minimum Value: 0 (#1), 16 (#2)
Maximum Value: 15 (#1), 31 (#2)
Default Value: 8
Description: This parameter performs two functions. It determines
which bit of the two Digital Input Fast parameters will be controlled by
Digital In7 (Terminal TB3-49). Entering a value of 0 – 15 will control
bits 0 – 15 of the Digital Input 1 Fast (param 400), while entering a
value of 16 – 31 will control bits 0 – 15 of the Digital Input 2 Fast
(param 405). Refer to the description of Digital In 1 for more
information on programming. Connecting Digital In 7 to a positive
control voltage will cause the specified bit to be set to 1.
Parameter 590 – [A > Digital In 8]
Parameter 540 – [B > Digital In 8]
Use : Maps Digital Input 8
Programming Terminal units: None
Minimum Value: 0 (#1), 16 (#2)
Maximum Value: 15 (#1), 31 (#2)
Default Value: 0
Description: This parameter performs two functions. It determines
which bit of the two Digital Input Fast parameters will be controlled by
Digital In 8 (Terminal TB3-50). Entering a value of 0 – 15 will control
bits 0 – 15 of the Digital Input 1 Fast (param 400), while entering a
value of 16 – 31 will control bits 0 – 15 of the Digital Input 2 Fast
(param 405). Refer to the description of Digital In 1 for more
information on programming. Connecting Digital In 8 to a positive
control voltage will cause the specified bit to be set to 1.