Chapter 5

Programming Parameters

5-14

Parameter 561 – [A > Digital Out 4]
Parameter 511 – [B > Digital Out 4]

Use : Maps Digital Output 4
Programming Terminal units: None
Minimum Value: 0 (#1), 16 (#2)
Maximum Value: 15 (#1), 31 (#2)
Default Value: 8
Description: This parameter determines which bit of one of the two
Digital Output fast parameters will control Digital Output 4. Entering a
bit value of 0 – 15 will cause the Digital Output 1 (par 450) to control
digital out 1. Entering a bit value of 16 – 31 will cause the Digital
Output 2 (par 454) to control digital out 1. When the bit value is 1, this
output will be high.

Parameter 562 – [A > Digital Out 5]
Parameter 512 – [B > Digital Out 5]

Use : Maps Digital Output 5
Programming Terminal units: None
Minimum Value: 0 (#1), 16 (#2)
Maximum Value: 15 (#1), 31 (#2)
Default Value: 9
Description: This parameter determines which bit of one of the two
Digital Output fast parameters will control Digital Output 5. Entering a
bit value of 0 – 15 will cause the Digital Output 1 (par 450) to control
digital out 1. Entering a bit value of 16 – 31 will cause the Digital
Output 2 (par 454) to control digital out 1. When the bit value is 1, this
output will be high.

15

0

BIT 1

31

16

BIT 1

450

454

16 Bits

16 Bits

Digital Out 2

Control

Digital Out 1

Control