Power wiring – Rockwell Automation 25B PowerFlex 520-Series Adjustable Frequency AC Drive Quick Start User Manual
Page 9
Rockwell Automation Publication 520-QS001A-EN-E - March 2014
9
PowerFlex 520-Series Adjustable Frequency AC Drive
Power Wiring
Power Terminal Block Diagrams and Wiring Specifications
Recommended Shielded Wire
Location
Rating/Type
Description
Standard (Option 1)
600V, 90 °C (194 °F) XHHW2/RHW-2
Anixter B209500-B209507, Belden 29501-29507, or equivalent
• Four tinned copper conductors with XLPE insulation.
• Copper braid/aluminum foil combination shield and tinned copper drain wire.
• PVC jacket.
Standard (Option 2)
Tray rated 600V, 90 °C (194 °F)
RHH/RHW-2 Anixter OLF-7xxxxx or equivalent
• Three tinned copper conductors with XLPE insulation.
• 5 mil single helical copper tape (25% overlap min.) with three bare copper grounds
in contact with shield.
• PVC jacket.
Class I & II; Division I & II
Tray rated 600V, 90 °C (194 °F)
RHH/RHW-2 Anixter 7V-7xxxx-3G or equivalent
• Three bare copper conductors with XLPE insulation and impervious corrugated
continuously welded aluminum armor.
• Black sunlight resistant PVC jacket overall.
• Three copper grounds on #10 AWG and smaller.
Input Power Conditions
Input Power Condition
Corrective Action
Low Line Impedance (less than 1% line reactance)
• Install Line Reactor
(2)
• or Isolation Transformer
(2) See Appendix B of the PowerFlex 520-Series Adjustable Frequency AC Drive User Manual, publication
for accessory ordering information.
Greater than 120 kVA supply transformer
Line has power factor correction capacitors
• Install Line Reactor
(2)
• or Isolation Transformer
Line has frequent power interruptions
Line has intermittent noise spikes in excess of 6000V (lightning)
Phase to ground voltage exceeds 125% of normal line to line voltage
• Remove MOV jumper to ground.
• or Install Isolation Transformer with grounded secondary if necessary.
Ungrounded distribution system
240V open delta configuration (stinger leg)
(1)
(1) For drives applied on an open delta with a middle phase grounded neutral system, the phase opposite the phase that is tapped in the middle to the neutral or earth is referred to as the “stinger leg,” “high
leg,” “red leg,” etc. This leg should be identified throughout the system with red or orange tape on the wire at each connection point. The stinger leg should be connected to the center Phase B on the
reactor. See Appendix B of the PowerFlex 520-Series Adjustable Frequency AC Drive User Manual, publicat
Install Line Reactor
(2)
V/T2
T/L3
S/L2
R/L1
U/T1
W/T3
BR+
BR-
DC- DC+
V/T2
T/L3
S/L2
R/L1
U/T1
W/T3
BR+
BR-
DC-
DC+
Frame A...D
Frame E
Terminal
Description
R/L1, S/L2
1-Phase Input Line Voltage Connection
R/L1, S/L2, T/L3
3-Phase Input Line Voltage Connection
U/T1, V/T2, W/T3
Motor Phase
Connection =
Switch any two motor leads to change
forward direction.
DC+, DC-
DC Bus Connection (except for 110V 1-Phase)
BR+, BR-
Dynamic Brake Resistor Connection
Safety Ground – PE
Frame
Maximum Wire Size
(1)
(1) Maximum/minimum sizes that the terminal block will accept – these are not recommendations.
Minimum Wire Size
(1)
Torque
A
5.3 mm
2
(10 AWG)
0.8 mm
2
(18 AWG)
1.76...2.16 Nm (15.6...19.1 lb-in.)
B
8.4 mm
2
(8 AWG)
2.1 mm
2
(14 AWG)
1.76...2.16 Nm (15.6...19.1 lb-in.)
C
8.4 mm
2
(8 AWG)
2.1 mm
2
(14 AWG)
1.76...2.16 Nm (15.6...19.1 lb-in.)
D
13.3 mm
2
(6 AWG)
5.3 mm
2
(10 AWG)
1.76...2.16 Nm (15.6...19.1 lb-in.)
E
26.7 mm
2
(3 AWG)
8.4 mm
2
(8 AWG)
3.09...3.77 Nm (27.3...33.4 lb-in.)