Rockwell Automation 25B PowerFlex 520-Series Adjustable Frequency AC Drive Quick Start User Manual
Page 25
Rockwell Automation Publication 520-QS001A-EN-E - March 2014
25
PowerFlex 520-Series Adjustable Frequency AC Drive
A466
A478
[PID x Preload]
0.0/500.0 Hz
0.1 Hz
0.0 Hz
Sets the value used to preload the integral component on start or enable.
A467
A479
[PID x Invert Err]
0/1
0 = “Normal”
1 = “Inverted”
0 = “Normal”
Changes the sign of the PID error.
A481
[Process Disp Lo]
0.00/99.99
0.01
0.00
Sets the value displayed in b010 [Process Display] when the drive is running at P043 [Minimum Freq].
A482
[Process Disp Hi]
0.00/99.99
0.01
0.00
Sets the value displayed in b010 [Process Display] when the drive is running at P044 [Maximum Freq].
A483
[Testpoint Sel]
0/FFFF
1
400
Used by Rockwell Automation field service personnel.
A484
[Current Limit 1]
0.0/Drive Rated Amps x 1.5 (Normal Duty); Drive
Rated Amps x 1.8 (Heavy Duty)
0.1 A
Drive Rated Amps x 1.1
(Normal Duty); Drive Rated
Amps x 1.5 (Heavy Duty)
Maximum output current allowed before current limiting occurs.
A485
[Current Limit 2]
0.0/Drive Rated Amps x 1.5 (Normal Duty); Drive
Rated Amps x 1.8 (Heavy Duty)
0.1 A
Drive Rated Amps x 1.1
Maximum output current allowed before current limiting occurs.
A486
A488
[Shear Pinx Level]
0.0/(Drive Rated Amps x 2)
0.1 A
0.0 A (Disabled)
Sets the value of current at which the shear pin fault occurs after the time set in A487, A489 [Shear Pin x
Time]. Setting the value at 0.0 A disables this function.
A487
A489
[Shear Pin x Time]
0.00/30.00 s
0.01 s
0.00 s
Sets the continuous time the drive must be at or above the value set in A486, A488 [Shear Pinx Level]
before a shear pin fault occurs.
A490
[Load Loss Level]
0.0/Drive Rated Amps
0.1 A
0.0 A
Provides a software trip (Load Loss fault) when the current drops below this level for the time specified in
A491 [Load Loss Time].
A491
[Load Loss Time]
0/9999 s
1 s
0 s
Sets the required time for the current to be below A490 [Load Loss Level] before a Load Loss fault occurs
A492
[Stall Fault Time]
0/5
0 = “60 Seconds”
1 = “120 Seconds”
2 = “240 Seconds”
3 = “360 Seconds”
4 = “480 Seconds”
5 = “Flt Disabled”
0 = “60 Seconds”
Sets the time that the drive remains in stall mode before a fault is issued.
A493
[Motor OL Select]
0/2
0 = “No Derate”
1 = “Min. Derate”
2 = “Max. Derate”
0 = “No Derate”
Drive provides Class 10 overload protection. Settings 0...2 select the derating factor for the I
2
t overload
function.
A494
[Motor OL Ret]
0/1
0 = “Reset”
1 = “Save”
0 = “Reset
Selects whether the motor overload counter is saved on power-down or reset on power-up.
A495
[Drive OL Mode]
0/3
0 = “Disabled”
1 = “Reduce CLim”
2 = “Reduce PWM”
3 = “Both-PWM 1st”
3 = “Both-PWM 1st”
Determines how the drive handles overload conditions that would otherwise cause the drive to fault.
A496
[IR Voltage Drop]
0.0/600.0VAC
0.1VAC
Based on Drive Rating
Value of volts dropped across the resistance of the motor stator (autotune) for induction motor.
A497
[Flux Current Ref]
0.00/(Drive Rated Amps x 1.4)
0.01 A
Based on Drive Rating
This is the current necessary for full motor flux. The value should be set to the full speed no-load current of
the motor.
= Stop drive before changing this parameter.
= Parameter is specific to PowerFlex 525 drives only.
No.
Parameter
Min/Max
Display/Options
Default
PF 525
PF 525
PF 525
PF 525
PF 525
PF 525
PF 525
PF 525