Basic display group parameters – Rockwell Automation 25B PowerFlex 520-Series Adjustable Frequency AC Drive Quick Start User Manual
Page 18

18
Rockwell Automation Publication 520-QS001A-EN-E - March 2014
PowerFlex 520-Series Adjustable Frequency AC Drive
Basic Display Group Parameters
See the PowerFlex 520-Series Adjustable Frequency AC Drive User Manual, publication
descriptions of the parameters listed here, as well as the full list of available parameters.
No.
Parameter
Min/Max
Display/Options
b001
[Output Freq]
0.00/[Maximum Freq]
0.01 Hz
Output frequency present at T1, T2 & T3 (U, V & W). Does not include slip frequency.
b002
[Commanded Freq]
0.00/[Maximum Freq]
0.01 Hz
Value of the active frequency command even if the drive is not running.
Important: The frequency command can come from a number of sources.
b003
[Output Current]
0.00/(Drive Rated Amps x 2)
0.01 A
Output current present at T1, T2 & T3 (U, V & W).
b004
[Output Voltage]
0.0/Drive Rated Volts
0.1V
Output voltage present at T1, T2 & T3 (U, V & W).
b005
[DC Bus Voltage]
0/1200VDC
1VDC
Filtered DC bus voltage level of the drive.
b006
[Drive Status]
00000/11111
Digit 5
Digit 4
Digit 3
Digit 2
Digit 1
SafetyActive
(1)
Decelerating Accelerating Forward
Running
Present operating condition of the drive.
(1) Setting is specific to PowerFlex 525 drives only.
b007,
b008,
b009
[Fault x Code]
F0/F127
F0
A code that represents a drive fault. Codes appear in these parameters in the order they occur (b007
[Fault 1 Code] = the most recent fault). Repetitive faults are only recorded once.
See Fault and Diagnostic Group for more information.
b010
[Process Display]
0/9999
1
Output frequency scaled by [Process Disp Hi] and [Process Disp Lo].
b0012
[Control Source]
0000/2165
Digit 4, 3, & 2
Digit 1
Freq Command Source
Start Command Source
Active source of the Start Command and Frequency Command. Normally defined by the settings of
P046, P048, P050 [Start Source x] and P047, P049, P051 [Speed Referencex].
b013
[Contrl In Status]
0000/1111
Digit 4
Digit 3
Digit 2
Digit 1
DB Trans On
(1)
DigIn TBlk 3 DigIn TBlk 2 DigIn TBlk 1
State of the digital terminal blocks 1...3 and DB transistor.
Important: Actual control commands may come from a source other than the control terminal block.
(1) Setting is specific to PowerFlex 525 drives only.
b014
[Dig In Status]
0000/1111
Digit 4
Digit 3
Digit 2
Digit 1
DigIn TBlk 8
(1)
DigIn TBlk 7
(1)
DigIn TBlk 6 DigIn TBlk 5
State of the programmable digital inputs.
(1) Setting is specific to PowerFlex 525 drives only.
b015
[Output RPM]
0/24000 rpm
1 rpm
Current output frequency in rpm. Scale is based on P035 [Motor NP Poles].
b016
[Output Speed]
0.0/100.0%
0.1%
Current output frequency in %. Scale is 0% at 0.00 Hz to 100% at P044 [Maximum Freq].
b017
[Output Power]
0.00/(Drive Rated Power x 2)
0.01 kW
Output power present at T1, T2 & T3 (U, V & W).
b018
[Power Saved]
0.00/655.35 kW
0.01 kW
Instantaneous power savings of using this drive compared to an across the line starter.
b019
[Elapsed Run time]
0/65535 x 10 hr
1 = 10 hr
Accumulated time drive is outputting power. Time is displayed in 10 hour increments.
b020
[Average Power]
0.00/(Drive Rated Power x 2)
0.01 kW
Average power used by the motor since the last reset of the meters.
b021
[Elapsed kWh]
0.0/100.0 kWh
0.1 kWh
Accumulated output energy of the drive. When the maximum value of this parameter is reached, it
resets to zero and b022 [Elapsed MWh] is incremented.