Powerflex 525 control i/o wiring block diagram – Rockwell Automation 25B PowerFlex 520-Series Adjustable Frequency AC Drive Quick Start User Manual
Page 13
Rockwell Automation Publication 520-QS001A-EN-E - March 2014
13
PowerFlex 520-Series Adjustable Frequency AC Drive
PowerFlex 525 Control I/O Wiring Block Diagram
04
05
06
07
01
02
03
08
11
12
13
14
15
16
17
18
19
Digital Common
DigIn TermBlk 05
DigIn TermBlk 06
DigIn TermBlk 07/Pulse
Stop
(1)
DigIn TermBlk 02/
Start/Run FWD
(2)
DigIn TermBlk 03/
Direction/Run REV
DigIn TermBlk 08
R1
R2
S1
S2
S+
Relay 1 N.O.
Relay 1 Common
+24V DC
+10V DC
0-10V (or ±10V) Input
Analog Common
4-20mA Input
Analog Output
Opto Output 1
Opto Output 2
RJ45 Shield
Comm Common
Opto Common
+24V
+10V
Safety 1
Safety 2
Safety +24V
Typical
SNK wiring
Typical
SRC wiring
R1
S1
S2
S+
11
12
13
14
15
16
17
18
19
R2
R5
R6
01
02
03
04
05
06
07
08
C1
C2
30V DC
50 mA
Non-inductive
Common
24V
(3)
Pot must be
1...10 k ohm
2 W min.
0-10V
0/4-20 mA
SNK
D
igital In
D
igIn T
ermBlk
07
Se
l
Analog O
u
t
J10
J9
J5
Pulse In
SRC
Digital
Input
0/4-20mA
0-10V
SRC
SNK
R5
R6
Relay 2 Common
Relay 2 N.C.
C1
C2
Safe-Torque-Off
(1)
(2) Two wire control shown. For three wire control use a momentary input
on I/O Terminal 02 to command a start. Use a maintained input
for I/O Terminal 03 to change direction.
(3) Only one analog frequency source may be connected at a time. If more than one reference is connected at the same time, an undetermined frequency reference will result.
IMPORTANT
I/O Terminal 01 is always a stop input. The stopping mode is determined by the drive setting.
The drive is shipped with a jumper installed between I/O Terminals 01 and 11. Remove this jumper when using I/O
Terminal 01 as a stop or enable input.