Drive ratings – Rockwell Automation 25B PowerFlex 520-Series Adjustable Frequency AC Drive Quick Start User Manual
Page 31
Rockwell Automation Publication 520-QS001A-EN-E - March 2014
31
PowerFlex 520-Series Adjustable Frequency AC Drive
Drive Ratings
F109
Mismatch C-P
Set P053 [Reset To Defalts] to 3 “Power Reset”.
F110
Keypad Membrane
• Cycle power.
• Replace control module if fault cannot be cleared.
F111
(1)
Safety Hardware
• Check safety input signals. If not using safety, verify and tighten jumper for I/O terminals S1, S2 and S+.
• Replace control module if fault cannot be cleared.
F114
uC Failure
• Cycle power.
• Replace control module if fault cannot be cleared.
F122
I/O Board Fail
• Cycle power.
• Replace drive or control module if fault cannot be cleared.
F125
Flash Update Req
Perform a firmware flash update operation to attempt to load a valid set of firmware.
F126
NonRecoverablErr
• Clear fault or cycle power to the drive.
• Replace drive or control module if fault cannot be cleared.
F127
DSIFlashUpdatReq
Perform a firmware flash update operation using DSI communications to attempt to load a valid set of firmware.
(1) This fault is not applicable to PowerFlex 523 drives.
PowerFlex 523 Frames – Ratings are in kW and (HP).
Fram
e
1-Phase
100...120V
1-Phase
200...240V
1-Phase
200...240V
w/ Filter
3-Phase
200...240V
3-Phase
380...480V
3-Phase
380...480V
w/ Filter
3-Phase
525...600V
A
0.2...0.4 (0.25...0.5)
0.2...0.75 (0.25...1.0)
0.2...0.75 (0.25...1.0)
0.2...2.2 (0.25...3.0)
0.4...2.2 (0.5...3.0)
0.4...2.2 (0.5...3.0)
0.4...2.2 (0.5...3.0)
B
0.75...1.1 (1.0...1.5)
1.5...2.2 (2.0...3.0)
1.5...2.2 (2.0...3.0)
4.0 (5.0)
4.0 (5.0)
4.0 (5.0)
4.0 (5.0)
C
–
–
–
5.5 (7.5)
5.5...7.5 (7.5...10.0)
5.5...7.5 (7.5...10.0)
5.5...7.5 (7.5...10.0)
D
–
–
–
7.5 (10.0)
11.0...15.0 (15.0...20.0)
11.0...15.0 (15.0...20.0)
11.0...15.0 (15.0...20.0)
E
–
–
–
11.0...15.0 (15.0...20.0)
–
18.5...22.0 (25.0...30.0)
18.5...22.0 (25.0...30.0)
PowerFlex 525 Frames – Ratings are in kW and (HP).
Fram
e
1-Phase
100...120V
1-Phase
200...240V
1-Phase
200...240V
w/ Filter
3-Phase
200...240V
3-Phase
380...480V
3-Phase
380...480V
w/ Filter
3-Phase
525...600V
A
0.4 (0.5)
0.4...0.75 (0.5...1.0)
0.4...0.75 (0.5...1.0)
0.4...2.2 (0.5...3.0)
0.4...2.2 (0.5...3.0)
0.4...2.2 (0.5...3.0)
0.4...2.2 (0.5...3.0)
B
0.75...1.1 (1.0...1.5)
1.5...2.2 (2.0...3.0)
1.5...2.2 (2.0...3.0)
4.0 (5.0)
4.0 (5.0)
4.0 (5.0)
4.0 (5.0)
C
–
–
–
5.5 (7.5)
5.5...7.5 (7.5...10.0)
5.5...7.5 (7.5...10.0)
5.5...7.5 (7.5...10.0)
D
–
–
–
7.5 (10.0)
11.0...15.0 (15.0...20.0)
11.0...15.0 (15.0...20.0)
11.0...15.0 (15.0...20.0)
E
–
–
–
11.0...15.0 (15.0...20.0)
–
18.5...22.0 (25.0...30.0)
18.5...22.0 (25.0...30.0)
No.
Fault
Action