Drive Ratings

F109

Mismatch C-P

Set P053 [Reset To Defalts] to 3 “Power Reset”.

F110

Keypad Membrane

Cycle power.
Replace control module if fault cannot be cleared.

F111

(1)

Safety Hardware

Check safety input signals. If not using safety, verify and tighten jumper for I/O terminals S1, S2 and S+.
Replace control module if fault cannot be cleared.

F114

uC Failure

Cycle power.
Replace control module if fault cannot be cleared.

F122

I/O Board Fail

Cycle power.
Replace drive or control module if fault cannot be cleared.

F125

Flash Update Req

Perform a firmware flash update operation to attempt to load a valid set of firmware.

F126

NonRecoverablErr

Clear fault or cycle power to the drive.
Replace drive or control module if fault cannot be cleared.

F127

DSIFlashUpdatReq

Perform a firmware flash update operation using DSI communications to attempt to load a valid set of firmware.

(1) This fault is not applicable to PowerFlex 523 drives.

PowerFlex 523 Frames – Ratings are in kW and (HP).

Fram

e

1-Phase
100...120V

1-Phase
200...240V

1-Phase
200...240V
w/ Filter

3-Phase
200...240V

3-Phase
380...480V

3-Phase
380...480V
w/ Filter

3-Phase
525...600V

A

0.2...0.4 (0.25...0.5)

0.2...0.75 (0.25...1.0)

0.2...0.75 (0.25...1.0)

0.2...2.2 (0.25...3.0)

0.4...2.2 (0.5...3.0)

0.4...2.2 (0.5...3.0)

0.4...2.2 (0.5...3.0)

B

0.75...1.1 (1.0...1.5)

1.5...2.2 (2.0...3.0)

1.5...2.2 (2.0...3.0)

4.0 (5.0)

4.0 (5.0)

4.0 (5.0)

4.0 (5.0)

C

5.5 (7.5)

5.5...7.5 (7.5...10.0)

5.5...7.5 (7.5...10.0)

5.5...7.5 (7.5...10.0)

D

7.5 (10.0)

11.0...15.0 (15.0...20.0)

11.0...15.0 (15.0...20.0)

11.0...15.0 (15.0...20.0)

E

11.0...15.0 (15.0...20.0)

18.5...22.0 (25.0...30.0)

18.5...22.0 (25.0...30.0)

PowerFlex 525 Frames – Ratings are in kW and (HP).

Fram

e

1-Phase
100...120V

1-Phase
200...240V

1-Phase
200...240V
w/ Filter

3-Phase
200...240V

3-Phase
380...480V

3-Phase
380...480V
w/ Filter

3-Phase
525...600V

A

0.4 (0.5)

0.4...0.75 (0.5...1.0)

0.4...0.75 (0.5...1.0)

0.4...2.2 (0.5...3.0)

0.4...2.2 (0.5...3.0)

0.4...2.2 (0.5...3.0)

0.4...2.2 (0.5...3.0)

B

0.75...1.1 (1.0...1.5)

1.5...2.2 (2.0...3.0)

1.5...2.2 (2.0...3.0)

4.0 (5.0)

4.0 (5.0)

4.0 (5.0)

4.0 (5.0)

C

5.5 (7.5)

5.5...7.5 (7.5...10.0)

5.5...7.5 (7.5...10.0)

5.5...7.5 (7.5...10.0)

D

7.5 (10.0)

11.0...15.0 (15.0...20.0)

11.0...15.0 (15.0...20.0)

11.0...15.0 (15.0...20.0)

E

11.0...15.0 (15.0...20.0)

18.5...22.0 (25.0...30.0)

18.5...22.0 (25.0...30.0)

No.

Fault

Action

This manual is related to the following products: