12

Rockwell Automation Publication 520-QS001A-EN-E - March 2014

PowerFlex 520-Series Adjustable Frequency AC Drive

PowerFlex 523 Control I/O Terminal Designations

No.

Signal

Default

Description

Parameter

R1

Relay N.O.

Fault

Normally open contact for output relay.

t076

R2

Relay Common

Fault

Common for output relay.

t081

R3

Relay N.C.

Motor Running

Normally closed contact for output relay.

P045

01

Stop

Coast

Three wire stop. However, it functions as a stop under all input modes and cannot be disabled.

P045, P046,
P048, P050,
A544, t062

02

DigIn TermBlk 02/
Start/Run FWD

Run FWD

Used to initiate motion and also can be used as a programmable digital input. It can be programmed with t062 [DigIn
TermBlk 02] as three wire (Start/Dir with Stop) or two wire (Run FWD/Run REV) control. Current consumption is 6 mA.

t063

03

DigIn TermBlk 03/
Dir/Run REV

Run REV

Used to initiate motion and also can be used as a programmable digital input. It can be programmed with t063 [DigIn
TermBlk 03] as three wire (Start/Dir with Stop) or two wire (Run FWD/Run REV) control. Current consumption is 6 mA.

t063

04

Digital Common

Return for digital I/O. Electrically isolated (along with the digital I/O) from the rest of the drive.

05

DigIn TermBlk 05/
Pulse In

Preset Freq

Program with t065 [DigIn TermBlk 05]. Also functions as a Pulse Train input for reference or speed feedback. The
maximum frequency is 100 kHz. Current consumption is 6 mA.

t065

06

DigIn TermBlk 06

Preset Freq

Program with t066 [DigIn TermBlk 06]. Current consumption is 6 mA.

t066

11

+24V DC

Referenced to Digital Common. Drive supplied power for digital inputs. Maximum output current is 100 mA.

12

+10V DC

Referenced to Analog Common. Drive supplied power for 0...10V external potentiometer.
Maximum output current is 15 mA.

P047, P049

13

0-10V In

(1)

(1) Only one analog frequency source may be connected at a time. If more than one reference is connected at the same time, an undetermined frequency reference will result.

Not Active

For external 0-10V (unipolar) input supply or potentiometer wiper.
Input impedance: Voltage source = 100 kW

Allowable potentiometer resistance range = 1...10 kW

P047, P049,
t062, t063,
t065, t066,
t093, A459,
A471

14

Analog Common

Return for the analog I/O. Electrically isolated (along with the analog I/O) from the rest of the drive.

15

4-20mA In

(1)

Not Active

For external 4-20 mA input supply.
Input impedance = 250 W

P047, P049,
t062, t063,
t065, t066,
A459, A471

C1

C1

This terminal is tied to the RJ-45 port shield. Tie this terminal to a clean ground in order to improve noise immunity
when using external communication peripherals.

C2

C2

This is the signal common for the communication signals.