Smart start-up with basic program group parameters, Smart start-up with basic program group – Rockwell Automation 25B PowerFlex 520-Series Adjustable Frequency AC Drive Quick Start User Manual
Page 20
20
Rockwell Automation Publication 520-QS001A-EN-E - March 2014
PowerFlex 520-Series Adjustable Frequency AC Drive
Smart Start-Up with Basic Program Group Parameters
The PowerFlex 520-series drive is designed so that start-up is simple and efficient. The Basic Program group contains the
most commonly used parameters. See the PowerFlex 520-Series Adjustable Frequency AC Drive User Manual, publication
for detailed descriptions of the parameters listed here, as well as the full list of available parameters.
= Stop drive before changing this parameter.
= Parameter is specific to PowerFlex 525 drives only.
No.
Parameter
Min/Max
Display/Options
Default
P030
[Language]
1/15
1 = English
2 = Français
3 = Español
4 = Italiano
5 = Deutsch
6 = Reserved
7 = Português
8 = Reserved
9 = Reserved
10 = Reserved
11 = Reserved
12 = Polish
13 = Reserved
14 = Turkish
15 = Czech
1
Selects the language displayed.
Important: The setting takes effect after the drive is power cycled.
P031
[Motor NP Volts]
10V (for 200V Drives), 20V (for 400V Drives),
25V (for 600V Drives) / Drive Rated Volts
1V
Based on Drive Rating
Sets the motor nameplate rated volts.
P032
[Motor NP Hertz]
15/500 Hz
0.1 A
60 Hz
Sets the motor nameplate rated frequency.
P033
[Motor OL Current]
0.0/(Drive Rated Amps x 2)
0.1 A
Based on Drive Rating
Sets the motor nameplate overload current.
P034
[Motor NP FLA]
0.0/(Drive Rated Amps x 2)
0.1 A
Drive Rated Amps
Sets the motor nameplate FLA.
P035
[Motor NP Poles]
2/40
1
4
Sets the number of poles in the motor.
P036
[Motor NP RPM]
0/24000 rpm
1 rpm
1750 rpm
Sets the rated nameplate rpm of motor.
P037
[Motor NP Power]
0.00/Drive Rated Power
0.01 kW
Drive Rated Power
Sets the motor nameplate power. Used in PM regulator.
P038
[Voltage Class]
2/3
2 = “480V”
3 = “600V”
3
Sets the voltage class of 600V drives. Only applicable to 600V drives.
P039
[Torque Perf Mode]
0/3
0 = “V/Hz”
1 = “SVC”
2 = “Economize”
3 = “Vector”
(1)
1
Selects the motor control mode.
(1) Setting is specific to PowerFlex 525 drives only.
P040
[Autotune]
0/2
0 = “Ready/Idle”
1 = “Static Tune”
2 = “Rotate Tune”
0
Enables a static (not spinning) or dynamic (motor spinning) autotune.
P041
[Accel Time 1]
0.00/600.00 s
0.01 s
10.00 s
Sets the time for the drive to accel from 0 Hz to
[Maximum Freq].
P042
[Decel Time 1]
0.00/600.00 s
0.01 s
10.00 s
Sets the time for the drive to decel from [Maximum
Freq] to 0 Hz.
PF 525
PF 525