25A-D013N114
25B-D013N114
7.5
5.5
7.5
5.5
13.0
323...528
14.1
15.4
20/35
100-C23
140M-D8E-C20
–
175.0
25A-D017N114
25B-D017N114
10.0
7.5
10.0
7.5
17.0
323...528
16.8
18.4
25/40
100-C23
140M-D8E-C20
–
230.0
25A-D024N114
25B-D024N114
15.0
11.0
15.0
11.0
24.0
323...528
24.1
26.4
35/63
100-C37
140M-F8E-C32
656.7
(7)
313.0
25A-D030N114
25B-D030N114
20.0
15.0
15.0
11.0
30.0
323...528
30.2
33.0
45/70
100-C43
140M-F8E-C45
656.7
(7)
402.0
25A-D037N114
25B-D037N114
25.0
18.5
20.0
15.0
37.0
323...528
30.8
33.7
45/70
100-C43
140M-F8E-C45
–
602.0
25A-D043N114
25B-D043N114
30.0
22.0
25.0
18.5
43.0
323...528
35.6
38.9
50/80
100-C60
140M-F8E-C45
–
697.0
525...600V AC (-15%, +10%) – 3-Phase Input, 0...575V 3-Phase Output
25A-E0P9N104
25B-E0P9N104
0.5
0.4
0.5
0.4
0.9
446...660
1.4
1.2
3/6
100-C09
140M-C2E-B25
–
22.0
25A-E1P7N104
25B-E1P7N104
1.0
0.75
1.0
0.75
1.7
446...660
2.6
2.3
3/6
100-C09
140M-C2E-B25
–
32.0
25A-E3P0N104
25B-E3P0N104
2.0
1.5
2.0
1.5
3.0
446...660
4.3
3.8
6/10
100-C09
140M-C2E-B40
–
50.0
25A-E4P2N104
25B-E4P2N104
3.0
2.2
3.0
2.2
4.2
446...660
6.1
5.3
10/16
100-C09
140M-D8E-B63
–
65.0
25A-E6P6N104
25B-E6P6N104
5.0
4.0
5.0
4.0
6.6
446...660
9.1
8.0
10/20
100-C09
140M-D8E-C10
–
95.0
25A-E9P9N104
25B-E9P9N104
7.5
5.5
7.5
5.5
9.9
446...660
12.8
11.2
16/25
100-C16
140M-D8E-C16
(6)
–
138.0
25A-E012N104
25B-E012N104
10.0
7.5
10.0
7.5
12.0
446...660
15.4
13.5
20/32
100-C23
140M-D8E-C16
–
164.0
25A-E019N104
25B-E019N104
15.0
11.0
15.0
11.0
19.0
446...660
27.4
24.0
32/50
100-C30
140M-F8E-C25
656.7
(7)
290.0
25A-E022N104
25B-E022N104
20.0
15.0
15.0
11.0
22.0
446...660
31.2
27.3
35/63
100-C30
140M-F8E-C32
656.7
(7)
336.0
25A-E027N104
25B-E027N104
25.0
18.5
20.0
15.0
27.0
446...660
28.2
24.7
35/50
100-C30
140M-F8E-C32
1416.0
(7)
466.0
25A-E032N104
25B-E032N104
30.0
22.0
25.0
18.5
32.0
446...660
33.4
29.2
40/63
100-C37
140M-F8E-C32
1416.0
(7)
562.0
(1)
Normal Duty (ND) and Heavy Duty (HD) ratings are available for this drive.
(2) When the drive is controlling motors with lower amp ratings, refer to the drive nameplate for drive input current rating.
(3) The AIC ratings of the Bulletin 140M Motor Protector Circuit Breakers may vary. See Bulletin 140M Motor Protection Circuit Breakers Application Ratings.
(4) Bulletin 140M with adjustable current range should have the current trip set to the minimum range that the device will not trip.
(5) Manual Self-Protected (Type E) Combination Motor Controller, UL listed for 480Y/277 and 600Y/347 AC input. Not UL listed for use on 480V or 600V Delta/Delta, corner ground, or high-resistance ground
systems.
(6) When used with the 140M circuit breaker, the 25A-E9P9104 must be installed in a ventilated or non-ventilated enclosure with the minimum size of 457.2 x 457.2 x 269.8 mm (18 x 18 x 10.62 in.).
(7) When using a Manual Self-Protected (Type E) Combination Motor Controller with this drive power rating, the drive must be installed in a ventilated or non-ventilated enclosure with the minimum volume
specified in this column. Application specific thermal considerations may require a larger enclosure.
Catalog No.
(1)
Output Ratings
Input Ratings
Branch Circuit Protection
Mi
n. Enc
los
ur
e
Vo
lum
e (in.
3
)
IP 2
0 Open
T
ype
Wa
tt
s L
os
s
PowerFlex
523
PowerFlex
525
Normal Duty
Heavy Duty
Amps
Voltage
Range
kVA
Max
Amps
(2)
Fuse
Ratings
Min/Max
Contactors
140M Motor
Protectors
(3)
(4)
(5)
HP
kW
HP
kW