Phase Rebalance

As little as 4% supply voltage unbalance can result in a 20% current
unbalance and a 25% increase in motor temperature, possibly
triggering a premature failure of the motor. The SMC Dialog Plus
controller continuously monitors the incoming three-phase line
voltage balance and adjusts the output voltage automatically to
balance the three-phase currents drawn by the motor.

Figure 3.9 Phase Rebalance

Notes: (1) Phase Rebalance is not active during bypass operation.

(2) Phase rebalance requires the use of the converter modul

(Bulletin 825) and fanning strip (Cat. No. 150-NFS).

Metering

The SMC Dialog Plus controller contains several power monitoring
parameters as standard. These parameters include:

Three-phase Current

Three-phase Voltage

Power in kW

Power Usage in kWH

Power Factor

Elapsed Time

Motor Thermal Capacity Usage

Fault Indication

The SMC Dialog Plus controller monitors both the pre-start and
running modes. If the controller senses a fault, the SMC Dialog Plus
controller shuts down the motor and displays the appropriate fault
condition in the LCD display. The controller monitors the following
conditions:

Open Gate

Line Fault

Undervoltage

Underload

Overvoltage

Excessive Starts/Hour

Voltage Unbalance

Overtemperature

Phase Reversal

Stall

Power Loss

Jam

Overload

System

Any fault condition will cause the auxiliary contacts to change state
and the hold-in circuit to release.

SMC Dialog Plus

Supply

Voltage

501V

480V

462V

Motor