Output idle action - parameter 13, Output idle value - parameter 14, Autobaud - parameter 15 – Rockwell Automation 800F DeviceNet Pendant Stations User Manual
Page 35

Operations
4–5
Publication 800-UM001A-EN-P – June 2004
OUTPUT IDLE ACTION – Parameter 13
In normal operation, the device shall permit configuration of the
Output Idle Action. This tells the device what to do with the output in
the case of an idle state. If Idle Value is selected, the device refers to
parameter 14, Output Idle Value, for action on an idle state. The
default for Output Idle Value is Idle Value.
OUTPUT IDLE VALUE – Parameter 14
In normal operation, the device shall permit configuration of the
Output Idle Value. If parameter 13, Output Idle Action is set to Idle
Value, this parameter tells the device what to do with the output in the
case of an idle state. The default for Output Idle Value is Idle Output
Off.
AUTOBAUD – Parameter 15
In normal operation, the device shall permit disabling of the
Autobaud feature. The default value for this parameter is Enabled.
Value
Idle Action
0
Idle Value
1
Hold Last State
Value
Idle Value
0
Idle Output Off
1
Idle Output On
Value
Function
0
Enabled
1
Disabled