3–8

Installation and Wiring

Connecting the Communication
Cable to the Module

Follow these steps to connect your module.

1.

Verify that the cable/connector is correctly wired (see Figure 3.6
and Figure 3.7).

2.

Locate the D-shell connector at the base of the PD1 Module.

3.

Plug cable/connector into the PD1 D-shell connector and secure.

Figure 3.8
Profibus Connection

* Termination is required at both ends of the network.
The Profibus master might offer on-board termination.
Make sure that other Profibus slaves with on-board termination are set
up correctly.

Profibus Network Termination

The network must be terminated at the first (network master) and the
last PD1 module. A bus cable connector with an internal resistor
network must be used as no internal termination is provied on the
PD1 module. (Refer to Figure 3.7).

Profibus
Master

PLC

Profibus-DP

SSC160-C

Profibus-DP

SSC160-C

Profibus-DP

SSC160-C

Network
Termination
Resistor *

Internal
Network
Termination
Resistor