beautypg.com

Warning, Notice – Burnham 8H User Manual

Page 7

background image

b. If result is less than 50 ft

3

per 1,000 Btuh, space

is considered a confined space.

4. Determine building type. A building of unusually

tight construction has the following characteristics:
a. Walls and ceiling exposed to outside atmosphere

have a continuous water vapor retarder with a

rating of 1 perm or less with openings gasketed

and sealed, and

b. Weather-stripping has been added on openable

windows and doors, and

c. Caulking or sealants applied in joints around

window and door frames, between sole

plates and floors, between wall-ceiling joints,

between wall panels, at plumbing and electrical

penetrations, and at other openings.

5. For boiler located in an

unconfined space in a

building of other than unusually tight construction,

adequate combustion and ventilation air is normally

provided by fresh air infiltration through cracks

around windows and doors.

6. For boiler located in an unconfined space in a

building of unusually tight construction or in

a confined space, provide outdoor air through

permanent opening(s) which communicate directly

or by duct with the outdoors or spaces (crawl or

attic) freely communicating with the outdoors.

Minimum dimension of air opening(s) is 3” (7.6

cm).
a. Two permanent openings: Locate one opening

within 12 inches (30.5 cm) of top of space.

Locate remaining opening within 12 inches

(30.5 cm) of bottom of space. Size each opening

per following:
i. Direct communication with outdoors.

Minimum free area of each opening must be

1 square inch per 4,000 Btu per hour input

of all equipment in space.

ii. Vertical ducts. Minimum free area of each

opening must be 1 square inch per 4,000

Btu per hour input of all equipment in space.

Duct cross-sectional area shall be same as

opening free area.

iii. Horizontal ducts. Minimum free area of each

opening must be 1 square inch per 2,000

Btu per hour input of all equipment in space.

Duct cross-sectional area shall be same as

opening free area.

b. One permanent opening shall be permitted where

the boiler has clearances of at least 1” (2.5 cm)

from the sides and rear and 6” (15.2 cm) from

the front. Locate the opening within 12 inches

(30.5 cm) of top of space. Size opening per

following:

i. Minimum free area of 1 square inch per

3,000 Btu per hour input of all equipment in

space.

ii. Free area shall not be less than the sum

of the areas of all vent connectors in the

confined space.

Alternate method for boiler located within confined

space. Use indoor air if two permanent openings

communicate directly with additional space(s) of

sufficient volume such that combined volume of all

spaces meet criteria for unconfined space. Size each

opening for minimum free area of 1 square inch per

1,000 Btu per hour input of all equipment in spaces,

but not less than 100 square inches.

7. Ventilation Duct Louvers and Grilles. Equip outside

openings with louvers to prevent entrance of rain

and snow, and screens to prevent entrance of insects

and rodents. Louvers and grilles must be fixed in

open position or interlocked with equipment to open

automatically before burner operation. Screens must

not be smaller than ¼ inch mesh.

Consider the blocking effect of louvers, grilles and

screens when calculating the opening size to provide

the required free area. If free area of louver or grille

is not known, assume wood louvers have 20-25

percent free area and metal louvers and grilles have

60-75 percent free area.

8. For Specially Engineered Installations. The above

requirements shall be permitted to be waived

where special engineering, consistent with good

engineering practice and approved by the authority

having jurisdiction, provides an adequate supply of

air for combustion, ventilation, and dilution of flue

gases.

WARNING

Do not install boiler where gasoline or other

flammable vapors or liquids, or sources of

hydrocarbons (i.e. bleaches, cleaners, chemicals,

sprays, paint removers, fabric softeners, etc.) are

used or stored.

NOTICE

Mis-sizing of the boiler with regard to the heating

system load will result in excessive boiler cycling

and accelerated component failure. Burnham

DOES NOT warrant failures caused by mis-sized

boiler applications. DO NOT oversize the boiler

to the system. Modular/multiple boilers greatly

reduce the likelihood of boiler oversizing.