beautypg.com

Warning – Burnham 8H User Manual

Page 33

background image

33

Figure 2: Typical Vent System

9. Design vent system for sea level input.

10. Provide adequate ventilation of Boiler Room. See

Section I: Pre-Installation.

11. Never pass any portion of vent system through a

circulating air duct or plenum.

WARNING

When an existing boiler is removed from a

common venting system, the common venting

system is likely to be too large for proper venting

of the appliances remaining connected to it.

G.

If an Existing Boiler is Removed:

At the time of removal of an existing boiler,

the following steps shall be followed with each

appliance remaining connected to the common

venting system placed in operation, while the other

appliances remaining connected to the common

venting system are not in operation:

1. Seal any unused openings in the common venting

system.

2. Visually inspect the venting system for proper

size and horizontal pitch and determine there is no

blockage or restriction, leakage, corrosion, or other

deficiencies which could cause an unsafe condition.

3. Insofar as is practical, close all building doors and

windows and all doors between the space in which

the appliances remaining connected to the common

venting system are located and other spaces of the

building. Turn on clothes dryers and any appliance

not connected to the common venting system.

Turn on any exhaust fans, such as range-hoods and

bathroom exhausts, so they will operate at maximum

speed. Do not operate a summer exhaust fan. Close

fireplace dampers.

4. Place in operation the appliance being inspected.

Follow the Lighting (or Operating) Instructions.

Adjust thermostat so appliance will operate

continuously.

5. Test for spillage at the draft hood relief opening after

5 minutes of main burner operation. Use the flame

of a match or candle, or smoke from a cigarette,

cigar or pipe.

6. After it has been determined that each appliance

remaining connected to the common venting system

properly vents when tested as outlined above, return

doors, windows, exhaust fans, fireplace dampers and

any other gas-burning appliance to their previous

condition of use.

7. Any improper operation of the common venting

system should be corrected so the installation

conforms with the National Fuel Gas Code, NFPA

54/ANSI Z223.1. When resizing any portion of

the common venting system, the common venting

system should be resized to approach the minimum

size as determined using the appropriate tables in

Part 7 and Part 11 in the National Fuel Gas Code,

NFPA 54/ANSI Z223.1.