Burnham 8H User Manual
Page 64
64
Yellow LED
Flash Code
a
Indicates
Recommended Service Action
Heartbeat
Normal Flame Signal
N/A
2
Weak Flame Signal -
System will operate reliably but flame signal is less than
desired.
Note: This indication may flash temporarily during or
shortly after lightoff on some applications.
Perform routine maintenance to
assure optimum flame signal.
1
Marginal Flame Signal (less than 1.1 µA) -
System may not operate reliably over time. Service call
recommended.
Note: This indication may flash temporarily during or
shortly after lightoff on some applications.
Check gas supply, pilot burner, flame
sense wiring, contamination of flame rod,
burner ground connection.
OFF
No Flame or Flame Signal -
below minimum threshold for system operation.
N/A
a
Flash Code Descriptions
- Heartbeat: Constant ½ second bright, ½ second dim cycles.
- The flash code number signifies that the LED flashes X times at 2Hz, remains off for two seconds, and then repeats
sequence.
Honeywell EI Ignition Module Yellow LED Flame Codes