beautypg.com

Warning – Burnham 8H User Manual

Page 30

background image

30

Length

(Feet)

0.3 Inch w.c. Pressure Drop

0.5 Inch w.c. Pressure Drop

½

¾

1

½

¾

1

10

132

278

520

1,050

175

360

680

1,400

20

92

190

350

730

120

250

465

950

30

73

152

285

590

97

200

375

770

40

63

130

245

500

82

170

320

660

50

56

115

215

440

73

151

285

580

60

50

105

195

400

66

138

260

530

70

46

96

180

370

61

125

240

490

80

43

90

170

350

57

118

220

460

90

40

84

160

320

53

110

205

430

100

38

79

150

305

50

103

195

400

Table 6: Maximum Capacity of Schedule 40 Pipe in CFH for Gas Pressures of 0.5 psig or Less

Table 7: Equivalent Lengths of Standard Pipe Fittings & Valves

Pipe

Size

I.D.

(Inches)

Valves (Fully Open)

Threaded Fittings

Gate

Globe

Angle

Swing

Check

90°

Elbow

45°

Elbow

90° Tee, Flow

Through Run

90° Tee, Flow

Through Branch

½”

0.622

0.35

18.6

9.3

4.3

1.6

0.78

1.0

3.1

¾”

0.824

0.44

23.1

11.5

5.3

2.1

0.97

1.4

4.1

1”

1.049

0.56

29.4

14.7

6.8

2.6

1.23

1.8

5.3

1¼”

1.380

0.74

38.6

19.3

8.9

3.5

1.6

2.3

6.9

Specific

Gravity

Correction

Factor

Specific

Gravity

Correction

Factor

0.50

1.10

1.30

1.07

0.55

1.04

1.40

1.04

0.60

1.00

1.50

1.00

0.65

0.96

1.60

0.97

0.70

0.93

1.70

0.94

0.75

0.90

---

---

0.80

0.87

---

---

Table 8: Specific Gravity Correction Factors

WARNING

Do not use matches, candles, open flames, or

other ignition source.

Figure 24: Recommended Gas Piping

C.

Pressure Test. The boiler and its gas connection must

be leak tested before placing boiler in operation.
1. Protect boiler gas valve. For all testing over ½ psig,

boiler and its individual shut-off valve must be

disconnected from gas supply piping. For testing at

½ psig or less, isolate boiler from gas supply piping

by closing boiler’s individual manual shut-off valve.

2. Locate leaks using approved combustible gas

detector, soap and water, or similar nonflammable

solution.