6

IX. Service

WARNING

Service on this boiler should be undertaken only by trained and skilled personnel from a qualified service

agency. Inspections should be performed at intervals specified in this manual. Maintain manual in a

legible condition.
Keep boiler area clear and free of combustible materials, gasoline and other flammable vapors and

liquids.
Do not place any obstructions in boiler room that will hinder flow of combustion and ventilation air.
The service instructions contained in this manual are in addition to the instructions provided by the

manufacturer of the boiler components. Follow component manufacturer’s instructions. Component

manufacturer’s instructions were provided with the boiler. Contact component manufacturer for replace-

ment if instructions are missing. Do not install, start up, operate, maintain or service this boiler without

reading and understanding all of the component instructions. Do not allow the boiler to operate with

altered, disconnected or jumpered components. Only use replacement components identical to those

originally supplied by Burnham Commercial.

A.

General. Inspection and service must be conducted

annually. Turn off electrical power and gas supply while

conducting service or maintenance. Follow instructions

TO TURN OFF GAS TO APPLIANCE. See Lighting/

Operating Instructions on inside of Front Removable

Door.

WARNING

Label all wires prior to disconnection when

servicing controls. Wiring errors can cause

improper and dangerous operation. Verify proper

operation after servicing.

B.

Maintenance of Low Water Cut-off (if used). Follow

instructions provided with low water cut-off.

C.

Vent System. Check for:

1. obstructions
2. accumulations of soot
3. deterioration of vent pipe or vent accessories due to

condensation or other reasons

4. proper support—no sags, particularly in horizontal

runs

5. tightness of joints. Remove all accumulations of

soot with wire brush and vacuum

Remove all obstructions. Replace all deteriorated parts

and support properly. Seal all joints.

D.

Remove Main Burners for cleaning, changing orifice

plugs, or repairs.
1. Shut down gas boiler in accordance with Lighting/

Operating Instructions on inside of Front Removable

Door. Close Manual Shut-off Valve.

2. Remove Front Removable Door. Raise Lower Front

Tie Bar.

3. Disconnect ignition system.

4. Remove burner access panel(s).
5. Mark location of Main Burner with Pilot Bracket on

manifold.

6. Remove hitch pin clips from Main Burner Orifices.
7. Hold Main Burner on throat. Lift slightly to raise

rear of burner. Push to rear of boiler until burner

clears Main Burner Orifice. Lift burners out.

8. Check burners to be sure they do not contain foreign

matter or restrictions. Clean burners with a soft

bristle brush, blow any dirt out with compressed air

or use a vacuum cleaner. See Figure 53.

E.

Clean Boiler Flueways. See Figure 53.

1. Shut down gas boiler in accordance with Lighting/

Operating Instructions on inside of Front Removable

Door. Close Manual Shut-off Valve.

2. Disconnect vent system. Remove Draft Hood.
3. Remove Jacket Top Panel.
4. Remove Canopy from top of boiler.
5. Lift Flue Baffles out of flueways. Remove any

accumulated scale or soot.

6. Thoroughly clean flueways with flue brush,

removing all scale and soot. See Figure 53.

7. Clean boiler heating surface accessible from

combustion chamber with straight handle wire

brush.

8. Reinsert Blue Baffles into flueways. See Figure 53

for correct baffle orientation. Tabs at top of each

baffle should rest o top of Flue Pins.

9. Install Canopy. See Section II: Boiler Assembly,

Paragraph G.

10. Install Jacket Top Panel, Draft Hood, Vent Damper

(if used) and Vent System.