Caution, Warning – Burnham 8H User Manual

Page 32

background image

32

E.

Boiler Equipped With Vent Damper. See Figure 26.

1. Open Vent Damper Carton and remove Installation

Instructions. Read Installation Instructions

thoroughly before proceeding.

CAUTION

Do not use one vent damper to control two or

more heating appliances.

2. Vent damper must be same size as draft hood

outlet. See Figure 1. Unpack vent damper carefully.

Forcing vent damper open or closed may damage

gear train and void warranty. Vent damper assembly

includes pre-wired connection harness with

polarized plug.

3. Mount vent damper assembly on draft hood without

modification to either (Refer to instructions packed

with vent damper for specific instructions). Vent

damper position indicator to be visible to users.

WARNING

Provide adequate clearance for servicing -

provide 6” minimum clearance between damper

and combustible construction.

F.

Install Vent Connector from draft hood or vent

damper to chimney. See Figure 27.
1. Do not connect into same leg of chimney serving an

open fireplace.

Figure 26: Vent Damper Installation

2. Where two or more appliances vent into a common

vent, the area of the common vent should at least

equal the area of the largest vent plus 50 % of the

area of the additional vents. Do not connect the

vent of this appliance into any portion of mechanical

draft system operating under positive pressure.

3. Vent connector should have the greatest possible

initial rise above the draft hood consistent with the

head room available and the required clearance from

adjacent combustible building structure.

4. Install vent connector above bottom of chimney to

prevent blockage - inspect chimney for obstructions

or restrictions and remove - clean chimney if

necessary.

5. Vent connector should slope upward from draft hood

to chimney not less than one inch in four feet. No

portion of vent connector should run downward or

have dips or sags. Vent connector must be securely

supported.

6. Use thimble where vent connector enters masonry

chimney - keep vent connector flush with inside of

flue liner.

7. Do not install Non-listed (AGA, CGA, CSA, ETL,

or UL) vent damper or other obstruction in vent

pipe.

8. Locate Boiler as close to Chimney as possible

consistent with necessary clearances. See Section I:

Pre-Installation.