Burnham 8H User Manual

Page 27

background image

2

2. If boiler is connected to heating coils located in

air handling units where they may be exposed to

refrigerated air, boiler piping must be equipped with

flow control valves to prevent gravity circulation of

boiler water during cooling system operation.

3. The piping diagrams shown (Figure 23, Detail “A”

and Detail “B”) are recommended for optimum

operation and long term reliability.

Burnham Commercial recommends maintaining

temperature differential (drop) across the system

at 40°F or less, and return water temperature at

minimum of 135°F.

Continued boiler operation for prolonged periods of

time under conditions when temperature differential

across the system exceeds 40°F and/or return water

temperature stays below 135°F, may result in

premature boiler failure due to flue gas condensation

and/or thermal shock.

Pump flow rates and minimum boiler supply and

return pipe sizes are shown in Table 4.

Figure 23: Recommended Boiler Piping for Circulator Zoned Heating Systems

Detail “A”: Blend Pump Piping

Detail “B”: Primary/Secondary Piping

with By-Pass