5

BOILER OPERATING INSTRUCTIONS

TO SHUT DOWN:

1. Close manual main shut-off valve(s) and pilot

valve(s).

2. Turn off main electric switch.

TO START UP:

1. Make sure that both the main manual and the pilot

valve(s) have been off for at least five minutes.

2. Turn room thermostat and all operating controls to

lowest setting.

3. Remove burner access panel(s).
4. Open manual pilot valve(s).

NOTE:

Item (5) applies only to boilers with standing pilot

safety switch(es).

5. Depress button on standing pilot safety switch and

hold lighted match to pilot, holding button in for at

least one minute or until pilot remains lighted after

button is released. Repeat for remaining standing

pilots.

6. Turn on main electric switch.
7. Reset safety switch on flame safeguard relay.
8. Immediately light constant burning rectification pilot(s)

Q179D with a lighted match. If pilot is not lighted

in 15 seconds, Step (7) must be repeated. Electric

pilot valve(s) are automatic, opening after Step (7).

(“OP” System).

8a. Intermittent electric ignition rectification pilot(s)

Q179C light up automatically when thermostat or

operating control calls for heat. (“EP” System).

9. Replace burner access panel(s).
10. Open manual main shut-off valve(s).
11. Adjust room thermostat and operating controls to

desired setting.

Figure 4: Lighting / Operating Instructions (OP/EP-CSD-)