beautypg.com

Mixing box control installation manual – Titus Mixing Box Controls IOM User Manual

Page 9

background image

Mixing Box Control Installation Manual

IOM-MBC-00

08-30-04

9 of 15

Figure 10. Economizer Control System Schematic

Installation

When planning the installation, allow ample clearance for

maintenance and service. Ensure the location is protected

from rain and snow. The following steps provide basic

instructions to install a damper motor.

1. Position damper motor on mixing box where

mounting is desired. Figure 11 shows possible crank

arm rotation.

2. Use the damper motor holes as guides and drill four

holes into mixing box.

3. Secure the damper motor to mixing box using four

screws. Figure 12 shows a typical damper motor to

mixing box installation.

Settings and Adjustments

Once installed, review system requirements and settings.

Then make necessary adjustments using the following

information.
1. Run motor to fully closed position and disconnect 24

Vac from terminals TR and TR1.

2. Connect minimum position potentiometer to terminals P

and P1 (T and T1 are disconnected).

3. Reconnect 24 Vac to terminals TR and TR1 and adjust

potentiometer for desired minimum position.

Note: Possible 90 degree arm rotation, based on motor

positioning.

Figure 11. Crank Arm Rotation Limits

4. When an actuator mounted minimum position

potentiometer is used and a remote potentiometer is

NOT connected in series, utilize jumper terminals P

and P1 on the minimum position potentiometer.