background image

Mixing Box Control Installation Manual

IOM-MBC-00

08-30-04

10 of 15

Figure 12. Typical Damper Motor to Mixing Box

Installation

Verification

Operate the motor through its complete open-close stroke.

If necessary, release one of the previously tightened

linkage connections to prevent damage. Check for proper

operation, making sure that the linkage does not bind and

that the motor travels smoothly throughout its fully open

and fully closed positions. This motor checkout ensures:

The motor operates the load.

The motor responds properly to the controller.

There is no binding of the linkage or motor stalling at

any point of travel.

If motor does not operate properly, check for proper

voltage or mechanical binding in linkage or damper.
If questions arise regarding this product, contact your

distributor or Titus representative.

Logic Module – W7459A

The logic module provides the operation control to the

Damper Motor. Use the enthalpy set point of the logic

module to select air temperature and humidity suitable for

free cooling. Figure 13 depicts the logic module.

Remote Minimum Position Control

Remote control of the outdoor air dampers is desirable

when temporary additional ventilation may be required.

The potentiometer in the logic module controls the

minimum position of the dampers.

Operation

Tables 11 and 12 provide operating rating and specific

information.

Figure 13. Fully Modulating Logic Module

Table 11. Operational Ratings

g

n

it

a

R

n

o

it

a

r

e

p

O

Operating ambient

temperature

25º Fahrenheit t

p

to

+125º Fahrenheit (32 to

+52º Celsius)

Humidity

5 to 95 percent relative

humidity

Input voltage

24 Vac, 50/60 hertz

Relay contact rating at 24 Vac 1.5 A run, 3.5 A inrush
Discharge air temperature

input

Single-pole, single-throw

(spst)

Minimum position

potentiometer adjustment

None
(Minimum position

adjustment is built into

damper motor M7415A)

Terminals for remote

minimum damper position

None

Output relays

2 Single-pole, double-

throw (spdt)

Application

To be used with

Solid-state enthalphy

sensor C7400A

Modulating damper

motor M7415A

Installation

The logic module mounts on the side of the Modulating

Damper Motor (W7415A). When planning the installation,

allow ample clearance for maintenance and service.

Ensure the location is protected from rain and snow.

1. Align logic module to prongs of the Damper Motor

and press module and motor together.

2. Secure logic module to damper motor using the

supplied mounting screw.