Mixing box control installation manual – Titus Mixing Box Controls IOM User Manual
Page 3

Mixing Box Control Installation Manual
IOM-MBC-00
08-30-04
3 of 15
Figure 2. Three-Position Damper Motor
Operation Ratings
The following table highlights operational information.
Table 2. Operating Ratings
Operation
Rating
Synchronous
Normally closed
Power VA
7
Timing (sec.)
90
Stroke
90 degrees, opens counter-
clockwise as viewed from power
end.
Application
Three-position, with adjustable
minimum position control
Timing
90 seconds
Voltage and
frequency
24 Vac, 50/60 hertz
Maximum operating
torque
25-inch/pound (2.8N-M)
Ambient temperature
rating
-25° to +125° Fahrenheit (-32° to
+52° Celsius) at 25 percent duty
cycle.
Shaft
Single-ended drive with crank arm
supplied.
Approximate
dimensions
4.5 inches (114 millimeter) high; 5
inches (127 millimeters) wide, and
5.188 inches (132 millimeter)
deep.
Component recognized by Underwriters Laboratories, Inc.
Installation
When planning the installation, allow ample clearance for
maintenance and service. Ensure the location is protected
from rain and snow. The following steps provide basic
instructions to install a damper motor.
1.
Position damper motor on mixing box where
mounting is desired.
Note: Motor placement may restrict crank arm
rotation. Position motor to allow widest range
of crank arm rotation, see Figure 3.
2.
Use the damper motor holes as guides and
drill four holes into mixing box.
3.
Secure the damper motor to mixing box using
four screws. Figure 4 shows a typical damper
motor to mixing box installation.
Note: Possible 90 degree arm rotation, based on
motor positioning.
Figure 3. Crank Arm Rotation Limits
Figure 4. Typical Damper Motor to Mixing Box
Installation