Figure 2. Three-Position Damper Motor

Operation Ratings

The following table highlights operational information.

Table 2. Operating Ratings

Operation

Rating

Synchronous

Normally closed

Power VA

7

Timing (sec.)

90

Stroke

90 degrees, opens counter-

clockwise as viewed from power

end.

Application

Three-position, with adjustable

minimum position control

Timing

90 seconds

Voltage and

frequency

24 Vac, 50/60 hertz

Maximum operating

torque

25-inch/pound (2.8N-M)

Ambient temperature

rating

-25° to +125° Fahrenheit (-32° to

+52° Celsius) at 25 percent duty

cycle.

Shaft

Single-ended drive with crank arm

supplied.

Approximate

dimensions

4.5 inches (114 millimeter) high; 5

inches (127 millimeters) wide, and

5.188 inches (132 millimeter)

deep.

Component recognized by Underwriters Laboratories, Inc.

Installation

When planning the installation, allow ample clearance for

maintenance and service. Ensure the location is protected

from rain and snow. The following steps provide basic

instructions to install a damper motor.

1.

Position damper motor on mixing box where

mounting is desired.

Note: Motor placement may restrict crank arm

rotation. Position motor to allow widest range

of crank arm rotation, see Figure 3.

2.

Use the damper motor holes as guides and

drill four holes into mixing box.

3.

Secure the damper motor to mixing box using

four screws. Figure 4 shows a typical damper

motor to mixing box installation.

Note: Possible 90 degree arm rotation, based on

motor positioning.

Figure 3. Crank Arm Rotation Limits

Figure 4. Typical Damper Motor to Mixing Box

Installation