The sensor consists of thermistor sensor element used in

ventilation duct systems. Negative temperature coefficient

(NTC) causes the resistance to decrease as the sampled air

temperature increases. This resistance change is used to

control the W973 and W7415A. Setting and calibration not

required.

Operation

Table 15 highlights operational ratings of the air temperature

sensor.

Enthalpy Changeover Set Point

With single enthalpy the enthalpy changeover set point is set to

return the outdoor air damper to minimum position when the

enthalpy rises above its set point. The enthalpy set point scale

markings, located on W7459, are A, B, C, and D in Figure 20.

Figure 20. Performance Characteristics for Enthalpy Changeover Settings A, B, C, and D

Table 15. Operation Ratings

Specification

Performance

Maximum ambient

temperature

250º Fahrenheit (125º

Celsius)

Operating temperature

range

-30 to 150º Fahrenheit (-34 to

65º Celsius)

Resistance/ Temperature

(NTC)

300 ohms at 77º Fahrenheit

(25º Celsius)

Resistance sensitivity per

degree at midrange

70 ohms per degree

Fahrenheit

Electrical connections

¼-inch quick-connect

terminals