Mixing Box Control Installation Manual

IOM-MBC-00

08-30-04

4 of 15

Settings and Adjustments

1.

Connect 24 Vac to motor at terminals T and X

(Terminal D is not connected).

2.

Adjust thumbwheel on motor for desired minimum

position.

Operation

A single-pole, single-throw (SPST) low-voltage controller

is used to control the three-position Damper Motor.

Fully open – when controller provides 24 Vac to D

and T, motor is energized and drives fully open.

Fully closed – when power is removed from

terminals T and D, and the motor spring returns to the

fully closed position.

Mid-position – when controller provides 24 Vac to T

and X, motor is energized and drives to the adjustable

mid-position (minimum position).

An adjustable minimum position can be reached from

either the fully closed or fully open position. From fully

closed, the motor drives open to the minimum position;

from fully open the motor spring returns to the minimum

position.

Verification

Operate the motor through its complete open-close stroke.

If necessary, release one of the previously tightened

linkage connections to prevent damage. Check for proper

operation, ensuring the linkage does not bind and the

motor travels smoothly throughout its fully open and full

closed positions. This motor checkout ensures:

1.

The motor operates the load.

2.

The motor responds properly to the controller.

3.

There is no binding of the linkage or motor stalling

at any point of travel.

If motor does not operate properly, check for proper

voltage or mechanical binding in linkage or damper.
If questions arise regarding this product, contact your

distributor or Titus representative.

Logic Module – W7459C

The logic module provides control for the damper motor.

Use the enthalpy set point of the logic module to select air

temperature and humidity suitable for free cooling. Figure

5 depicts the logic module.

Remote Minimum Position Control

Remote control of the outdoor air dampers can be used, if

temporary additional ventilation is required. The

potentiometer in the logic module – W7459 controls the

minimum position of the dampers.

Operation

Table 4 provides operational information.

Figure 5. Three-Position Logic Module

Table 4. Operational Ratings

Operation

Rating

Operating ambient

temperature

25º Fahrenheit t

p

to +125º

Fahrenheit (32 to +52º Celsius)

Humidity

5 to 95 percent relative humidity

Input voltage

24 Vac, 50/60 hertz

Relay contact rating

at 24 Vac

1.5 A run, 3.5 A inrush

Application

Use with three-position Damper

Motor - M8405A

Discharge air

temperature input

Single-pole, single-throw (spst)

Minimum position

potentiometer

adjustment

None
(Minimum position adjustment is

built into Damper Motor M8405)

Terminals for remote

minimum damper

position

None

Output relays

2 single-pole, dual-throw (spdt)