beautypg.com

Mixing box control installation manual – Titus Mixing Box Controls IOM User Manual

Page 7

background image

Mixing Box Control Installation Manual

IOM-MBC-00

08-30-04

7 of 15

e

s

n

o

p

s

e

R

n

o

it

c

A

4. Turn enthalpy set

potentiometer to “A”.

LED should be on,

indicating low enthalpy.
Motor drives toward

open.

5. Turn enthalpy set point

potentiometer to “D”.

LED should be off,

indicating high enthalpy.
Motor spring returns to

fully closed position.

6. Disconnect the 1.2k ohm

checkout resistor.

C.

Sensor

1. Reconnect the + lead of

outdoor enthalpy sensor

to the + terminal of

W7459.

2. Connect a DC multi-meter

or voltmeter between

terminals S

O

of the W7459

and terminal S of the

enthalpy sensor. (Positive

meter lead to terminal S of

enthalpy sensor.)

Multi-meter or voltmeter

should indicate between

3 and 25 mA, if sensor

is operating properly.
If multi-meter or

voltmeter indicates

zero, the sensor may be

wired backwards.

3. If using differential

enthalpy, the return air

enthalpy sensor may be

checked by connecting a

DC multi-meter or

voltmeter between

terminal S

R

of the W7459

and terminal S of the

return air enthalpy sensor.

(Position meter lead to

terminal S of return air

enthalpy sensor.

Multi-meter or voltmeter

should indicate between

3 and 25 mA, if sensor

is operating properly.
If multi-meter or

voltmeter indicates

zero, the sensor may be

wired backwards.