Mixing Box Control Installation Manual

IOM-MBC-00

08-30-04

8 of 15

Modulating Control System

Package contents of the modulating (enthalpy) system are

as follows:

Table 8. Modulating (Enthalpy) System Package

Part Code

Description

Quantity

M7415A

Modulating damper motor

1

W7459A

Logic module

1

C7400A

Solid state enthalpy sensor

1

C7150B

Sensor

1

27518

Ball joints

2

27520E

18-inch pushrods

2

Modulating Damper Motor – M7415A

Spring-return, 25-inch/pound damper motor provides

modulating control of economizer systems or ventilation

dampers. Spring returns motor shaft to normal position on

power interruption. Figure 9 depicts a damper motor.

Operation

Tables 9 and 10 provide operating ratings and motor

performance respectively.
A single Damper Motor – M7415 accepts the thermistor

sensor input from the air temperature sensor, mounted in

the discharge or mixed air duct. See Figure 10.
During the occupied period, on a call for cooling, when the

outdoor air temperature is low, the damper motor – M7415

modulates to maintain between 50 and 56° Fahrenheit at

the thermistor.
If the mixed or discharge air temperature is above 56°

Fahrenheit, the damper motor opens to admit additional

outdoor air until the temperature returns to between 50

and 56° Fahrenheit. If the mixed or discharge air

temperature is below 50° Fahrenheit, the damper motor

modulates close, shutting the outdoor air damper until the

temperature returns to between 50 and 56° Fahrenheit.

During the occupied period, the damper will not close past

the minimum position.
If the fully open damper motor cannot satisfy the space

demand, mechanical cooling is sequenced on.
During the unoccupied period, the damper motor overrides

the minimum position setting and drives fully closed. On a

loss of power, the damper spring returns to a fully closed

position.
When in heating operation, outdoor air temperature or

enthalpy conditions are high, economizer operation is

locked out, and the damper motor is held at minimum

position.

Figure 9. Fully Modulating Damper Motor

Table 9. Operation Ratings

Specification

Performance

Stroke

Fixed 90 degrees, opens counter-

clockwise as viewed from power

end.

Timing

90 seconds

Voltage and

frequency

24 Vac, 50/60 hertz

Maximum operating

torque

25 inch/pound (2.8N-M)

Ambient temperature

rating

-25° to +125° Fahrenheit (-32° to

+52° Celsius) at 25 percent duty

cycle.

Synchronous

Normally closed.

Power VA

8

Application

Modulating, use with thermistor

mixed-air or discharge sensor

(C7150B)

Shaft

Single-ended drive with crank arm

supplied.

Approximate

dimensions

4.5 inches (114 millimeter) high; 5

inches (127 millimeters) wide, and

5.188 inches (132 millimeter)

deep.

Component recognized by Underwriters Laboratories, Inc.