Mixing Box Control Installation Manual

IOM-MBC-00

08-30-04

5 of 15

Installation

The logic module mounts on the side of the three-position

damper motor (M8405A). When planning the installation,

allow enough clearance for maintenance and service.

Ensure the location is protected from rain and snow.

1.

Align logic module to prongs of the Damper Motor.

2.

Press logic module and Damper Motor together.

3.

Secure logic module to damper motor using the

supplied mounting screw.

Settings and Adjustments

The minimum position potentiometer keeps the outdoor air

damper from closing completely during system operation

to provide ventilation. Figure 6 shows potentiometer

adjustment slots. Use a screwdriver to make adjustments.

1.

Connect 24 Vac at terminals TR and X (D is not

connected).

2.

Adjust thumbwheel on motor for desired minimum

position.

Wiring

Disconnect power supply before connecting wiring to

prevent electrical shock or equipment. All wiring must

comply with applicable local codes, ordinances, and

regulations. See Figure 7 for wiring diagram depicting the

three-position control system.

Solid-State Enthalpy Sensor - C7400A

The solid-state enthalpy sensor – the C7400A has a solid-

state element that senses temperature and humidity. It

combines solid-state enthalpy changeover control,

minimum damper position potentiometer and compressor

staging relays.
The solid-state enthalpy sensor – C7400A when used with

the Solid State Economizer Logic Module – W7459 and

three-position damper motor – M8405 helps to position

outdoor and return air dampers in economizer systems.

Figure 8 depicts the solid-state enthalpy sensor.
Use for enthalpy control as follows:

One sensor in outdoor air for single enthalpy control.

Two sensors, one in return air and one in outdoor air,

for differential enthalpy control.

Contact a Titus

representative, if specifications call for differential

enthalpy control.

The enthalpy set point of the logic module selects the air

temperature and humidity suitable for free cooling.

Operational Ratings

Table 6 highlights operational ratings.

Figure 6. Enthalpy Set Point Potentiometer (Three-

Position System)

Figure 7. Three-position Control System Circuit