My UnIT Won’T eXeCUTe a reMoTe MaChIne-To-MaChIne CoMManD .

• Machine-to-machine commands will not execute while you are connected

locally.

• The output on the remote unit you are trying to switch is not set to manual

mode.

• The input condition for the machine-to-machine command is not being met.
• The PIN and Password for the remote unit is programmed incorrectly.

My Cell682 ISn’T DISplayIng The CorreCT valUe froM My 4–20Ma

TranSDUCer .

• The analog input jumper isn’t set to the 4–20mA position.
• The analog input “type” isn’t set to 4–20mA in the software.
• The transducer is not wired correctly.
• The transducer is not calibrated for the desired measurement range.
• The analog input table values aren’t programmed to the calibrated range of

the transducer.

• The transducer is not compatible with single-ended inputs therefore an isola-

tion device is required.

My TeMperaTUre SenSor ISn’T DISplayIng The CorreCT valUe .

• The analog input jumper isn’t set to the Temperature position.
• The analog input “type” isn’t set to Temperature in the software
• The temperature sensor isn’t a compatible 2.8K or 10K thermistor.
• The temperature sensor isn’t wired correctly.

Why Don’T The valUeS DISplayeD on The Web page MaTCh The valUeS

DISplayeD In The Cell682 SofTWare?

• The web page displays a snapshot of the values at a particular moment in

time. It does not display real-time values, as is the case when connected
locally through the Cell682 software.

• Click the Status Update button on the web page to retrieve a current snap-

shot.

Why Can’T I geT pUMp ConTrol To Work?

• The Output(s) are not set to Pump Control mode.
• The Pump Control parameters are programmed incorrectly.
• The level transducer is not wired to analog input #6.
• The level transducer is not reading the proper values.