beautypg.com

Output wiring – Sensaphone CELL682 User Manual

Page 46

background image

44

Cell682 User’s Manual

oUtpUt wiring
The output relays on the Cell682 are for low current control signals (0.3A
120VAC/1.0A 24VDC maximum).
DO NOT directly connect the power for the pumps to these relays—THIS WILL
PERMANENTLY DAMAGE THE Cell682.
Use the Cell682 outputs to control intermediate motor contactors/relays that will
switch actual power to the pumps.

Figure 4: Output wiring to two pumps