Configuring the output operating mode, Switching the output, Output status & statistics – Sensaphone CELL682 User Manual
Page 41
39
Chapter 5: output programming
configUring the oUtpUt operating Mode
Click the drop-down arrow and select the operating mode for the output. You can
have the relay automatically turn on for a variety of alarm conditions, either indi-
vidual alarms or if any alarm occurs. When set to turn ON automatically on an
Alarm condition, it will remain ON until the alarm is acknowledged. If you will
be controlling the output manually or via a machine-to-machine command, select
Manual mode. If you will be using the output for fill or drain pump control, select
Pump Control. For simplex pump control set only one output to Pump Control
mode; for duplex pump control set both outputs to Pump Control mode. See
Chapter 6 for more information on pump control programming.
Figure 3: Output Operating mode
switching the oUtpUt
To manually turn an output on, click on the current state (On or Off) and select
the new state, then click OK. See the following screen.
Figure 4: Output manual select
oUtpUt statUs & statistics
The Cell682 software will display the current state of the output as well as the
number of times the relay has turned on, the total time the relay has been on
(cumulative), and the alarm status of the output (valid in pump control mode
only). This information can be useful for monitoring how often a device (pump,