Appendix D: Specifications

49

AppENdix d: SpECiFiCAtioNS

alaRm notIFICatIon mEthods:

• E-Mail, Text Message, SNMP Trap
• 8 Alarm escalation levels
• Comprehensive scheduling per input, user, and

alarm destination

dEstInatIons:

• 8 Programmable User Profiles
• 4 Programmable destinations per profile
• Alarms can be assigned to specific User Profiles

CommunICatIon typEs:

• E-Mail – SMTP
• Text Messages via SMTP
• Web page – HTTP
• SNMP – MIB with Traps, GET, GETNEXT, and

SET

• MODBUS®/TCP Slave Conformance Class 0

and 1

sEnsoRs:

• Up to 30 Wireless Sensors 
• Dry Contact - Normally Open /Normally

Closed

• Temperature - 2.8K Thermistor
• Water detection
• Humidity
• Power Failure
• 4-20mA Current Loop
• 12-Bit Resolution

CERtIFICatIon standaRds:

• FCC Part 15 – Class B Compliant Data logging
• 32,000 Samples (all samples include data, date,

and time)

• 1 second to 100 hours sampling rate, variable

rate per sensor

• User programmable sensor selection
• Battery
• Power Supply

CommunICatIon poRts:

• Ethernet 10/100Base–T

loCal IndICatoRs:

• 80 Character lighted LCD
• Ethernet link and Activity LEDs

powER REquIREmEnts:

• External transformer 120VAC 60Hz

input/9VDC Output

• Rechargeable Battery Backup (included)

wIRElEss tEChnology:

• 2.4GHz/ISM

opERatIng CondItIons:

• 0-50°C (32–122°F)
• 0-90% RH, non–condensing

physICal pRopERtIEs:

• 7.6” x 5.1” x 2.0” (19cm x 13cm x 5cm)
• 2.5 lbs (1.3kg)