beautypg.com

Sensaphone WSG30 System Users manual User Manual

Page 31

background image

Chapter 7: Wireless Sensors

31

Power suPPly wIrIng (router Mode)
When using your wireless sensor in Router mode, you must use an external power supply (Sensaphone

Part #XFR-0041). This is required because router mode uses more power than can be supplied by

batteries alone for an extended period of time. You can also use a power supply when the sensor is

configured as an End Point, which will greatly extend the life of the batteries and minimize the need to

change them.
To connect the power supply, remove the sensor cover and locate the screw terminals labeled “5V DC”.

connect the positive wire from the power supply to the “+” terminal. Plug the power supply into an

appropriate outlet.

1.375”

MountIng
The humidity sensor can be mounted directly on a flat surface.

Consideration should be given as to whether or not an electrical outlet will

be required if using the optional power supply. Mount the sensor as high as

possible to provide for optimal Wireless transmission. When installed within

a building where the Wireless signal must travel through several obstruc-

tions, the sensor should be located within 250’ of the WSG30 or within 300’

of a sensor/router.
Use a pencil to mark the hole locations at the top and bottom of the housing.

Install the drywall anchors (if necessary) to the wall. Attach the housing to

the wall using #6 tapping screws.

sPeCIFICatIons
Operating Temperature Range: 32° to 122° F (0° to 50° C)
Operating Humidity Range: 0- 90% RH non-condensing
Accuracy: ± 3% from 20-80% RH (± 5% otherwise)
Range (Indoor/Urban): Up to 300’ (90m)
Transmit Power Output: 100mW (20dBm)
Operating Frequency: ISM 2.4 GHz
Power: (2) AA alkaline batteries and/or 5VDC (300mA) plug-in adapter
Battery Life: Up to 2 years @ Sampling interval = 3 seconds
Dimensions: 3.1” x 3.8” x 1.1” (7.9cm x 9.8cm x 2.85cm)
Housing: White plastic

*Specifications subject to change without notice