beautypg.com

Sensaphone WSG30 System Users manual User Manual

Page 26

background image

WSG30 Users Manual

26

Escalation Priority: This can be set to any number between 1 and 8. Profiles set to escalation level 1 will

immediately receive alarm messages. Those set to higher escalation levels will have their alarm messages

delayed by the time entered for the Escalation Delay on the System Setup screen. If the alarm condition

resets or corrects itself before the Escalation delay expires then no message(s) will be sent to those users

with a higher escalation setting. This feature is useful for staggering alarm message delivery based on the

duration of the alarm condition.
Profile Delivery Schedule: This weekly schedule sets the time period(s) when alarm delivery will

be active for the selected Profile. The schedule is divided into half-hour increments over the seven

weekdays. A check mark indicates that alarm delivery is active for that time period.

ContaCt pRogRammIng
The WSG30 allows you to program up to 4 Contacts per Profile. The Contacts can be either: E-mail,

SMS-Text Message, or SNMP Trap. Each contact can have a programmable Schedule so that you only

receive messages when your Contact schedule is enabled. A Test button is also provided to check your

programming. To add a contact click the Add button:

Fig 11: Sample email contact programming

Fig 12: Sample SMS contact programming

Shown above are example screens for both email and SMS contacts. When selecting SMS be sure to

select the proper cellular carrier. A separate schedule can be programmed for each contact. Click Save

when finished. To test your programming click in the box next to each Contact you’d like to test, then

click the Test button.
To delete a contact, click the box next to the contact you would like to delete, then click the Delete

button.