Sensaphone WSG30 System Users manual User Manual
Page 26
WSG30 Users Manual
26
Escalation Priority: This can be set to any number between 1 and 8. Profiles set to escalation level 1 will
immediately receive alarm messages. Those set to higher escalation levels will have their alarm messages
delayed by the time entered for the Escalation Delay on the System Setup screen. If the alarm condition
resets or corrects itself before the Escalation delay expires then no message(s) will be sent to those users
with a higher escalation setting. This feature is useful for staggering alarm message delivery based on the
duration of the alarm condition.
Profile Delivery Schedule: This weekly schedule sets the time period(s) when alarm delivery will
be active for the selected Profile. The schedule is divided into half-hour increments over the seven
weekdays. A check mark indicates that alarm delivery is active for that time period.
ContaCt pRogRammIng
The WSG30 allows you to program up to 4 Contacts per Profile. The Contacts can be either: E-mail,
SMS-Text Message, or SNMP Trap. Each contact can have a programmable Schedule so that you only
receive messages when your Contact schedule is enabled. A Test button is also provided to check your
programming. To add a contact click the Add button:
Fig 11: Sample email contact programming
Fig 12: Sample SMS contact programming
Shown above are example screens for both email and SMS contacts. When selecting SMS be sure to
select the proper cellular carrier. A separate schedule can be programmed for each contact. Click Save
when finished. To test your programming click in the box next to each Contact you’d like to test, then
click the Test button.
To delete a contact, click the box next to the contact you would like to delete, then click the Delete
button.